SOLVIMUS_GE20_MBUS_VALUE
SOLVIMUS_GE20_MBUS_VALUE (FB)
SOLVIMUS_GE20_MBUS_VALUE (FB)FUNCTION_BLOCK SOLVIMUS_GE20_MBUS_VALUE
InOut:
Input
xEn
BOOL
TRUE
Enable / disable communication ( TRUE = enabled )
Input
byUnitId
BYTE
255
Address of the device (set via IP address) ( Default: 255 )
Input
xUpdateActual
BOOL
FALSE
Update of actual values (on every rising edge )
Input
wBaseAdressMbusDevice
WORD
10
Modbus - base register for the MBus device information
Input
wBaseAdressMbusValue
WORD
20
Modbus - base register for the MBus value information
Input
xResError
BOOL
FALSE
Reinitialization of the outputs ‘eErrorCodeCom’ to the no-error state (on each rising edge)
Inout
ModbusClient
ModbusClientBase
Client of the device
Output
liVal_Raw
LINT
Meter value in 64-bit integer format - signed - unscaled
Output
rVal_Raw_SF
REAL
Scaling factor for ‘liVal_Raw’
Output
liVal
LINT
Meter value in 64-bit integer format - signed - scaled ( = ‘liVal_Raw’ x scaling factor ‘rVal_Raw_SF’ )
Output
rVal
REAL
Meter value in 32-bit IEEE 754 floating point format - signed - scaled to ‘byValueUnit’ ( = final value )
Output
rVal_kWh
REAL
(‘rVal’ in kWh) x scaling factor ‘rVal_kWh_SF’
Output
eValUnit
SOLVIMUS_GE20_MBUS_UNIT_TYPE
Unit of the meter value
Output
dtSysTime
DT
Timestamp of the MBus device (UTC, in Germany UTC +1 / +2 h depending on summer/winter time)
Output
xAlarm
BOOL
FALSE
General fault ( TRUE = fault )
Output
xAlarmCom
BOOL
FALSE
General fault - communication ( TRUE = fault )
Output
eErrorCodeCom
ModbusErrorCode
Error code - communication ( 0 = no error )
Output
xBusy
BOOL
Communication indicator ( TRUE = communication )
Input Const
wBaseAdressMbusDeviceOffset
WORD
10
Offset for calculating the base address (Requirement: xBaseAdressMode = TRUE )
Input Const
xBaseAdressMode
BOOL
FALSE
Method of determining the base address:
Input Const
diAdrOffset
DINT
0
Offset for calculating Modbus addresses (from the Modbus registers) (permissible range: -1, 0, +1)
Input Const
rVal_kWh_SF
REAL
1.0
Scaling factor for the output ‘rVal_kWh’
Input Const
rVal_SF
REAL
1.0
Scaling factor for the output ‘rVal’
Input Const
tTimeUpdateActual
TIME
TIME#1m0s0ms
Update interval for operations influenced by the input 'xUpdateActual'
Last updated

