KP_MD15_MOD_N_HE_FULL
KP_MD15_MOD_N_HE_FULL (FB)
KP_MD15_MOD_N_HE_FULL (FB)FUNCTION_BLOCK KP_MD15_MOD_N_HE_FULL
Representation

InOut:
Input
xEn
BOOL
TRUE
Enable / disable of communication ( TRUE = enabled )
Input
byUnitId
BYTE
0
Address of the device ( 1… 247, default = factory setting )
Input
xUpdateActual
BOOL
FALSE
Update of actual values ( on every rising edge )
Input
xUpdateInfo
BOOL
FALSE
Update of information (on every rising edge)
Input
xUpdateSetp
BOOL
FALSE
Update of setpoint values ( on every rising edge )
Input
xResError
BOOL
FALSE
Reinitialization of the outputs ‘eErrorCodeCom’ and ‘sErrorCodeDev’ to the fault-free state (on each rising edge)
Input
rSetpPos
REAL
0.0
Setpoint - position in % (0.0 - 100.0 %) (0.0% = spindle extended)
Inout
ModbusClient
ModbusClientBase
Client of the device
Output
sSerialNumber
STRING
Device serial number
Output
wFirmwareVer
WORD
Firmware version of the device
Output
wHardwareVer
WORD
Hardware version of the device
Output
rSetpPositionFb
REAL
Setpoint - position in % (0.0 - 100.0 %) (0.0% = spindle extended) — feedback
Output
rPosition
REAL
Current position in % (0.0 - 100.0 %) (0.0% = spindle extended)
Output
eCommandFb
KP_MD15_MOD_N_HE_COMMAND_MODE
Current status of the actuator — feedback
Output
eOpModeFb
KP_MD15_MOD_N_HE_OP_MODE
Current operating mode of the actuator — feedback
Output
xAlarm
BOOL
FALSE
Collective fault ( TRUE = Fault )
Output
xAlarmCom
BOOL
FALSE
Collective fault - communication ( TRUE = Fault )
Output
eErrorCodeCom
ModbusErrorCode
Error code - communication ( 0 = no error )
Output
sErrorCodeDev
STRING
String with the numbers of active device errors (bit 0 = number 1, bit 1 = number 2, etc.)
Output
xBusy
BOOL
Communication indicator ( TRUE = Communication )
Input Const
rMaxPos
REAL
100.0
Current absolute maximum position in % (0.0 - 100.0 %) (0.0% = spindle extended)
Input Const
rMinPos
REAL
0.0
Current absolute minimum position in % (0.0 - 100.0 %) (0.0% = spindle extended)
Input Const
eOpMode
KP_MD15_MOD_N_HE_OP_MODE
KP_MD15_MOD_N_HE_OP_MODE.SETPOINT
Current operating mode 0 = Control via setpoint 1 = Open 2 = Closed 3 = Parameter ‘rMinPos’ 5 = Parameter ‘rMaxPos’ 6 = Room temperature control loop
Input Const
rBusFailPos
REAL
100.0
Current position in % (0.0 - 100.0 %) (0.0% = spindle extended) in case of a bus failure (120 s)
Input Const
eBusFailMode
KP_MD15_MOD_N_HE_BUS_FAIL_MODE
KP_MD15_MOD_N_HE_BUS_FAIL_MODE.NO_DETECTION
Current operating mode in case of a bus failure 0 = no monitoring 1 = Closed after 120s without communication 2 = Open after 120s without communication 3 = Parameter ‘rBusFailPos’ after 120s without communication
Input Const
eCommand
KP_MD15_MOD_N_HE_COMMAND_MODE
KP_MD15_MOD_N_HE_COMMAND_MODE.NORMAL_MODE
Current status of the actuator 0 = Normal operation 1 = Adaptation / Initialization 2 = Test run = Manual flushing function (one-time full opening) 3 = Synchronization = Manual synchronization of end position 4 = Reset errors = Reset all errors in register 318 5 = Baud rate change = Transfer of parameters in registers 105 - 107
Input Const
tTimeUpdateSetp
TIME
TIME#45s0ms
Update interval for the operations influenced by the input ‘xUpdateSetp’
Input Const
tTimeUpdateInfo
TIME
TIME#0ms
Update interval for operations affected by the input 'xUpdateInfo'
Input Const
tTimeUpdateActual
TIME
TIME#3s0ms
Update interval for the operations influenced by the input ‘xUpdateActual’
Last updated

