EBM_SERIES_84_112_150_200_V6_0
EBM_SERIES_84_112_150_200_V6_0 (FB)
EBM_SERIES_84_112_150_200_V6_0 (FB)FUNCTION_BLOCK EBM_SERIES_84_112_150_200_V6_0
Representation

Notes on the fan firmware variant
The fan firmware variant can be read via a read access ( FC04 ) to register D000 ( = 53248 ). The following register values are currently valid ( 02.01.2023 ): 08 = V5_0 10 = V5_0 Lite 11 = V5_0 Lite and plug-in module 12 = V5_02 13 = V5_01 14 = V6_0 19 = V6_3\
Codesys
InOut:
Input
xEn
BOOL
TRUE
Enable / disable of communication ( TRUE = enabled )
Input
byUnitId
BYTE
0
Address of the device
Input
xUpdateActual
BOOL
FALSE
Update of actual values ( on every rising edge )
Input
xUpdateSetp
BOOL
FALSE
Update of setpoint values ( on every rising edge )
Input
xUpdateConfig
BOOL
FALSE
Update of the configuration (on every rising edge)
Input
xResError
BOOL
FALSE
Reinitialization of the outputs ‘eErrorCodeCom’, ‘stErrorCodeDev’ and ‘stWarningCodeDev’ to the fault-free state ( on each rising edge )
Input
xEnFan
BOOL
FALSE
Enable / disable of the fan ( FALSE = disabled )
Input
rSetp
REAL
0.0
Setpoint - fan ( 0.0 - 100.0% or absolute speed )
Input
xResErrorFan
BOOL
FALSE
Reset of active errors in the fan ( on each rising edge )
Inout
ModbusClient
ModbusClientBase
Client of the device
Output
sSerialNum
STRING
Serial number of the fan
Output
wIdentification
WORD
Type of electronics or protocol ( see documentation )
Output
xFanEnable
BOOL
State of the fan enable input ( TRUE = on )
Output
xOperationFan
BOOL
Operation indication of the fan ( FALSE = off )
Output
eParamSetFb
SERIES_84_112_150_200_PARAM_SET
SERIES_84_112_150_200_PARAM_SET.PARAM_SET_1
Currently selected parameter set
Output
eRotationFb
SERIES_84_112_150_200_ROTATION_MODE
SERIES_84_112_150_200_ROTATION_MODE.CLOCKWISE
Current direction of rotation
Output
rSetpFb
REAL
Feedback - current setpoint
Output
rSpeed
REAL
Current number of revolutions per minute
Output
rModLevel
REAL
Current modulation level ( 0.0 - 100.0% )
Output
rSpeedMax
REAL
Current maximum number of revolutions per minute
Output
rPower
REAL
Current power in X.X watts
Output
rPowerConsumpt
REAL
Energy consumption of the fan since delivery in kWh
Output
rDCLinkVolt
REAL
Current DC voltage in X.X volts
Output
rDCLinkCurrent
REAL
Current DC current in X.X A
Output
rModuleTemp
REAL
Current module temperature in XXX degrees Celsius
Output
rMotorTemp
REAL
Current motor temperature in XXX degrees Celsius
Output
rInteriorTemp
REAL
Current electronics temperature in XXX degrees Celsius
Output
xAlarm
BOOL
FALSE
Collective fault ( TRUE = Fault )
Output
xAlarmCom
BOOL
FALSE
Collective fault - communication ( TRUE = Fault )
Output
eErrorCodeCom
ModbusErrorCode
Error code - communication ( 0 = no error )
Output
stErrorCodeDev
STRING
String with the numbers of active device errors
Output
stWarningCodeDev
STRING
String with the numbers of the active device warnings
Output
xBusy
BOOL
Communication indicator ( TRUE = Communication )
Input Const
tTimeUpdatePasswort
TIME
TIME#3m0s0ms
Update interval for the password required for some write operations. The instance ‘Setpoints_0’ is called cyclically.
Input Const
tTimeEmergency
TIME
TIME#10s0ms
Time until emergency operation ( maximum 25.5 s )
Input Const
rSetpEmergency
REAL
0
Setpoint - fan ( 0.0 - 100.0% or absolute speed ) in emergency operation
Input Const
xOperationEmergency
BOOL
FALSE
General enable/disable of emergency operation ( FALSE = disabled )
Input Const
eRotationEmergency
SERIES_84_112_150_200_ROTATION_MODE
SERIES_84_112_150_200_ROTATION_MODE.CLOCKWISE
Direction of rotation of the fan in emergency operation
Input Const
sPasswort
STRING
‘epM EC’
Password for the user level ( ‘epM EC’ = Customer/OEM, it must always be 6 characters )
Input Const
eControlMode_Set2
SERIES_84_112_150_200_CONTROL_MODE
SERIES_84_112_150_200_CONTROL_MODE.MODULATION_CONTROL
Operating mode - parameter set 2 ( currently not used )
Input Const
eControlMode_Set1
SERIES_84_112_150_200_CONTROL_MODE
SERIES_84_112_150_200_CONTROL_MODE.MODULATION_CONTROL
Operating mode - parameter set 1
Input Const
eRotation
SERIES_84_112_150_200_ROTATION_MODE
SERIES_84_112_150_200_ROTATION_MODE.CLOCKWISE
Direction of rotation of the fan
Input Const
tTimeUpdateConfig
TIME
TIME#0ms
Update interval for operations affected by the input 'xUpdateConfig'
Input Const
tTimeUpdateSetp
TIME
TIME#45s0ms
Update interval for the operations influenced by the input ‘xUpdateSetp’
Input Const
tTimeUpdateActual
TIME
TIME#3s0ms
Update interval for the operations influenced by the input ‘xUpdateActual’
Last updated