DANFOSS_VLT_HVAC_DRIVE
DANFOSS_VLT_HVAC_DRIVE (FB)
DANFOSS_VLT_HVAC_DRIVE (FB)FUNCTION_BLOCK DANFOSS_VLT_HVAC_DRIVE
Representation

InOut:
Input
xEn
BOOL
TRUE
Enable / disable communication (TRUE = enable)
Input
byUnitId
BYTE
0
Device address (1 .. 247)
Input
xUpdateActual
BOOL
FALSE
Update of actual values (on every rising edge )
Input
xUpdateSetp
BOOL
FALSE
Update of setpoints (on every rising edge )
Input
xUpdateConfig
BOOL
FALSE
Update of the configuration (on each rising edge)
Input
xEnDevice
BOOL
FALSE
Enable / disable of the frequency converter (FALSE = Off)
Input
rSetp
REAL
0.0
Setpoint of the frequency converter (speed, setpoint) ( -100.0 - +100.0%)
Input
xResetShutdown
BOOL
FALSE
Reset of the device after a shutdown (on every rising edge)
Inout
ModbusClient
ModbusClientBase
Client of the device
Output
xFb
BOOL
Operating message (FALSE = Off, TRUE = On)
Output
rSetpPercFb
REAL
Feedback - Current setpoint in percent
Output
rOutputFreq
REAL
Current output frequency in Hz
Output
wControlWordFb
WORD
Feedback - Current control word
Output
wStatusWord
WORD
Current status word
Output
dwOperatingHours
DWORD
Motor operating hours
Output
dwElecEnergyTota
DWORD
Total electrical work in kWh
Output
dwCountSwitchOn
DWORD
Number of switch-ons
Output
rElecVoltage
REAL
Output voltage in volts
Output
rElecCurrent
REAL
Output current in amperes
Output
rThermalProtect
REAL
Thermal motor protection in percent
Output
xBit0_Control
BOOL
Status of the controller (FALSE = not ready, TRUE = ready )
Output
xBit1_FreqConv
BOOL
Status of the frequency converter (FALSE = not ready, TRUE = ready)
Output
xBit2_FreeRun
BOOL
Status of free run (FALSE = active, TRUE = motor in operation)
Output
xBit3_AlarmOff
BOOL
Status of the fault with shutdown (FALSE = not active, TRUE = active)
Output
xBit4_Alarm
BOOL
Status of the fault without shutdown (FALSE = not active, TRUE = active)
Output
xBit6_AlarmOffBl
BOOL
Status of the fault with shutdown and blocking (FALSE = not active, TRUE = active)
Output
xBit7_Warn
BOOL
Status of the warning (FALSE = not active, TRUE = active)
Output
xBit8_SetpActual
BOOL
Status of speed setpoint/actual value (FALSE = different, TRUE = equal)
Output
xBit9_LocalBus
BOOL
Status of local operation/bus control (FALSE = local operation, TRUE = bus control)
Output
xBit10_FreqLimit
BOOL
Status of the frequency limits (FALSE = frequency is outside, TRUE = frequency is within)
Output
xBit12_OverTInv
BOOL
Status of the inverter overtemperature message ( FALSE = Off, TRUE = On)
Output
xBit13_OverVolt
BOOL
Status of the overvoltage message (FALSE = Off, TRUE = On)
Output
xBit14_OverMomen
BOOL
Status of the overtorque message (FALSE = Off, TRUE = On )
Output
xBit15_OverTherm
BOOL
Status of the thermal protective devices (FALSE = no exceedance, TRUE = limit exceeded)
Output
xAlarm
BOOL
FALSE
Collective fault (TRUE = fault)
Output
xAlarmCom
BOOL
FALSE
Collective fault - communication (TRUE = fault)
Output
eErrorCodeCom
ModbusErrorCode
Error code - communication (0 = no error)
Output
dwErrorCode1Dev
DWORD
0
Alarm word 1 - Device
Output
dwErrorCode2Dev
DWORD
0
Alarm word 2 - Device
Output
dwWarnCode1Dev
DWORD
0
Warning word 1 - Device
Output
dwWarnCode2Dev
DWORD
0
Warning word 2 - Device
Output
dwStateCode1Dev
DWORD
0
Extended status word 1 - Device
Output
dwStateCode2Dev
DWORD
0
Extended status word 2 - Device
Output
xBusy
BOOL
Communication indicator (TRUE = communication)
Input Const
wControlMode
WORD
0
0 = speed control, 3 = PID controller
Input Const
xCW_Bit15
BOOL
FALSE
FALSE = No reversal, TRUE = Reversal
Input Const
xCW_Bit14
BOOL
FALSE
Most Significant Bit - parameter set selection (00 = parameter set 1)
Input Const
xCW_Bit13
BOOL
FALSE
Least Significant Bit - parameter set selection (00 = parameter set 1)
Input Const
xCW_Bit12
BOOL
FALSE
FALSE = Relay 02 not activated, TRUE = Relay 02 activated
Input Const
xCW_Bit11
BOOL
FALSE
FALSE = Relay 01 not activated, TRUE = Relay 01 activated
Input Const
xCW_Bit10
BOOL
TRUE
FALSE = data invalid 1, TRUE = data valid
Input Const
xCW_Bit9
BOOL
FALSE
FALSE = Ramp 1, TRUE = Ramp 2
Input Const
xCW_Bit8
BOOL
FALSE
FALSE = No function, TRUE = fixed speed JOG
Input Const
xCW_Bit5
BOOL
TRUE
FALSE = hold frequency output, TRUE = use ramp
Input Const
xCW_Bit1
BOOL
FALSE
Most Significant Bit - fixed setpoint selection (00 = setpoint 0)
Input Const
xCW_Bit0
BOOL
FALSE
Least Significant Bit - fixed setpoint selection (00 = setpoint 0)
Input Const
eDisableMode
VLT_HVAC_DRIVE_DISABLE_MODE
VLT_HVAC_DRIVE_DISABLE_MODE.FREE_RUN_STOP
Type of shutdown of the frequency converter
Input Const
eCWTimeoutMode
VLT_HVAC_DRIVE_CONTROL_WORD_TIMEOUT_MODE
VLT_HVAC_DRIVE_CONTROL_WORD_TIMEOUT_MODE.OFF
Function after a control word timeout
Input Const
tTimeUpdateCW
TIME
TIME#30s0ms
Update interval for transmission of the control word (CW = Control word)
Input Const
tTimeUpdateConfig
TIME
TIME#0ms
Update interval for the processes influenced by the input
xUpdateConfig influenced
Input Const
tTimeUpdateSetp
TIME
TIME#45s0ms
Update interval for the processes influenced by the input
xUpdateSetp influenced
Input Const
tTimeUpdateActual
TIME
TIME#3s0ms
Update interval for the processes influenced by the input
xUpdateActual influenced
Last updated

