DANFOSS_VLT_HVAC_DRIVE
DANFOSS_VLT_HVAC_DRIVE (FB)
DANFOSS_VLT_HVAC_DRIVE (FB)FUNCTION_BLOCK DANFOSS_VLT_HVAC_DRIVE
Representation

InOut:
Input
xEn
BOOL
TRUE
Enable / disable of communication ( TRUE = enabled )
Input
byUnitId
BYTE
0
Device address ( 1 .. 247 )
Input
xUpdateActual
BOOL
FALSE
Update of actual values ( on every rising edge )
Input
xUpdateSetp
BOOL
FALSE
Update of setpoint values ( on every rising edge )
Input
xUpdateConfig
BOOL
FALSE
Update of the configuration (on every rising edge)
Input
xEnDevice
BOOL
FALSE
Enable / disable of the frequency converter ( FALSE = Off )
Input
rSetp
REAL
0.0
Setpoint of the frequency converter ( speed setpoint ) ( -100.0 - +100.0% )
Input
xResetShutdown
BOOL
FALSE
Reset of the device after a shutdown ( on each rising edge )
Inout
ModbusClient
ModbusClientBase
Client of the device
Output
xFb
BOOL
Operation indication ( FALSE = Off, TRUE = On )
Output
rSetpPercFb
REAL
Feedback - current setpoint in percent
Output
rOutputFreq
REAL
Current output frequency in Hz
Output
wControlWordFb
WORD
Feedback - current control word
Output
wStatusWord
WORD
Current status word
Output
dwOperatingHours
DWORD
Motor running hours
Output
dwElecEnergyTota
DWORD
Total electrical energy in kWh
Output
dwCountSwitchOn
DWORD
Number of switch-ons
Output
rElecVoltage
REAL
Output voltage in volts
Output
rElecCurrent
REAL
Output current in amperes
Output
rThermalProtect
REAL
Thermal motor protection in percent
Output
xBit0_Control
BOOL
Control state ( FALSE = not ready, TRUE = ready )
Output
xBit1_FreqConv
BOOL
Frequency converter state ( FALSE = not ready, TRUE = ready )
Output
xBit2_FreeRun
BOOL
Free run state ( FALSE = active, TRUE = motor in operation )
Output
xBit3_AlarmOff
BOOL
State of fault with shutdown ( FALSE = not active, TRUE = active )
Output
xBit4_Alarm
BOOL
State of fault without shutdown ( FALSE = not active, TRUE = active )
Output
xBit6_AlarmOffBl
BOOL
State of fault with shutdown and lockout ( FALSE = not active, TRUE = active )
Output
xBit7_Warn
BOOL
Warning state ( FALSE = not active, TRUE = active )
Output
xBit8_SetpActual
BOOL
Setpoint/actual speed state ( FALSE = different, TRUE = equal )
Output
xBit9_LocalBus
BOOL
Local operation / bus control state ( FALSE = local operation, TRUE = bus control )
Output
xBit10_FreqLimit
BOOL
Frequency limits state ( FALSE = frequency is outside, TRUE = frequency is inside )
Output
xBit12_OverTInv
BOOL
Overtemperature indication of the inverter ( FALSE = Off, TRUE = On )
Output
xBit13_OverVolt
BOOL
Overvoltage indication state ( FALSE = Off, TRUE = On )
Output
xBit14_OverMomen
BOOL
Overtorque indication state ( FALSE = Off, TRUE = On )
Output
xBit15_OverTherm
BOOL
State of thermal protection devices ( FALSE = no exceedance, TRUE = threshold exceeded )
Output
xAlarm
BOOL
FALSE
Collective fault ( TRUE = Fault )
Output
xAlarmCom
BOOL
FALSE
Collective fault - communication ( TRUE = Fault )
Output
eErrorCodeCom
ModbusErrorCode
Error code - communication ( 0 = no error )
Output
dwErrorCode1Dev
DWORD
0
Alarm word 1 - device
Output
dwErrorCode2Dev
DWORD
0
Alarm word 2 - device
Output
dwWarnCode1Dev
DWORD
0
Warning word 1 - device
Output
dwWarnCode2Dev
DWORD
0
Warning word 2 - device
Output
dwStateCode1Dev
DWORD
0
Extended status word 1 - device
Output
dwStateCode2Dev
DWORD
0
Extended status word 2 - device
Output
xBusy
BOOL
Communication indicator ( TRUE = Communication )
Input Const
wControlMode
WORD
0
0 = Speed control, 3 = PID controller
Input Const
xCW_Bit15
BOOL
FALSE
FALSE = No reversal, TRUE = Reversal
Input Const
xCW_Bit14
BOOL
FALSE
Most Significant Bit - parameter set selection ( 00 = parameter set 1 )
Input Const
xCW_Bit13
BOOL
FALSE
Least Significant Bit - parameter set selection ( 00 = parameter set 1 )
Input Const
xCW_Bit12
BOOL
FALSE
FALSE = Relay 02 not activated, TRUE = Relay 02 activated
Input Const
xCW_Bit11
BOOL
FALSE
FALSE = Relay 01 not activated, TRUE = Relay 01 activated
Input Const
xCW_Bit10
BOOL
TRUE
FALSE = Data invalid 1, TRUE = Data valid
Input Const
xCW_Bit9
BOOL
FALSE
FALSE = Ramp 1, TRUE = Ramp 2
Input Const
xCW_Bit8
BOOL
FALSE
FALSE = No function, TRUE = Fixed speed JOG
Input Const
xCW_Bit5
BOOL
TRUE
FALSE = Hold frequency output, TRUE = use ramp
Input Const
xCW_Bit1
BOOL
FALSE
Most Significant Bit - fixed setpoint selection ( 00 = setpoint 0 )
Input Const
xCW_Bit0
BOOL
FALSE
Least Significant Bit - fixed setpoint selection ( 00 = setpoint 0 )
Input Const
eDisableMode
VLT_HVAC_DRIVE_DISABLE_MODE
VLT_HVAC_DRIVE_DISABLE_MODE.FREE_RUN_STOP
Type of shutdown of the frequency converter
Input Const
eCWTimeoutMode
VLT_HVAC_DRIVE_CONTROL_WORD_TIMEOUT_MODE
VLT_HVAC_DRIVE_CONTROL_WORD_TIMEOUT_MODE.OFF
Function after a timeout of the control word
Input Const
tTimeUpdateCW
TIME
TIME#30s0ms
Update interval for transmission of the control word ( CW = Control word )
Input Const
tTimeUpdateConfig
TIME
TIME#0ms
Update interval for operations affected by the input 'xUpdateConfig'
Input Const
tTimeUpdateSetp
TIME
TIME#45s0ms
Update interval for the operations influenced by the input ‘xUpdateSetp’
Input Const
tTimeUpdateActual
TIME
TIME#3s0ms
Update interval for the operations influenced by the input ‘xUpdateActual’
Last updated

