DANFOSS_NOVOCON
DANFOSS_NOVOCON (FB)
DANFOSS_NOVOCON (FB)FUNCTION_BLOCK DANFOSS_NOVOCON
InOut:
Input
xEn
BOOL
TRUE
Enable / disable communication ( TRUE = enabled )
Input
byUnitId
BYTE
0
Device address (1 .. 247)
Input
xUpdateActual
BOOL
FALSE
Update of actual values (on each rising edge ) (Range: operation)
Input
xUpdateSetp
BOOL
FALSE
Update of setpoint values (on every rising edge )
Input
xUpdateConfig
BOOL
FALSE
Update of the configuration ( on every rising edge )
Input
xUpdateInfo
BOOL
FALSE
Update of the information ( on every rising edge )
Input
xResDevice
BOOL
FALSE
Triggering of a warm reset (equivalent to switching off and on) (on every rising edge)
Input
xResError
BOOL
FALSE
Reinitialization of the outputs ‘eErrorCodeCom’ and/or ‘stErrorCodeDev’ to the no-error state (on every rising edge)
Input
xCoolMode
BOOL
FALSE
Enable / disable of cooling operation (FALSE = heating operation, TRUE = cooling operation)
Input
rSetpFlowRate
REAL
0.0
Setpoint - volumetric flow in the chosen unit ( eUnitSetpFlowRate)
Input
eMode
DANFOSS_NOVOCON_MODE
DANFOSS_NOVOCON_MODE.NORMAL_OPERATION
Operating mode of the actuator
Inout
ModbusClient
ModbusClientBase
Client of the device
Output
eModeFb
DANFOSS_NOVOCON_MODE
DANFOSS_NOVOCON_MODE.NORMAL_OPERATION
Operating mode of the actuator — feedback
Output
eValveTypeFb
DANFOSS_NOVOCON_VALVE_TYPE
Valve type — feedback
Output
rNominalFlowRate
REAL
Nominal volumetric flow of the selected valve (unit see 'Valve type selection' table)
Output
rDesignFlowRateHeatFb
REAL
Design volumetric flow for heating mode — feedback
Output
rDesignFlowRateCoolFb
REAL
Design volumetric flow for cooling mode — feedback
Output
eUnitDesignFlowRateFb
DANFOSS_NOVOCON_UNIT_DESIGN_FLOW_RATE
DANFOSS_NOVOCON_UNIT_DESIGN_FLOW_RATE.LITRES_PER_HOUR
Unit of the design volumetric flow — feedback
Output
rSetpFlowRateFb
REAL
Setpoint - volumetric flow in the chosen unit ( eUnitSetpFlowRate) — feedback
Output
eUnitSetpFlowRateFb
DANFOSS_NOVOCON_UNIT_SETP_FLOW_RATE
DANFOSS_NOVOCON_UNIT_SETP_FLOW_RATE.LITRES_PER_HOUR
Unit of the volumetric flow setpoint — feedback
Output
rActualFlowRate
REAL
Actual value - volumetric flow in the chosen unit ( eUnitActualFlowRate)
Output
eUnitActualFlowRateFb
DANFOSS_NOVOCON_UNIT_ACTUAL_FLOW_RATE
DANFOSS_NOVOCON_UNIT_ACTUAL_FLOW_RATE.LITRES_PER_HOUR
Unit of the actual volumetric flow — feedback
Output
rRelPos
REAL
Position of the actuator stem in % (Reference: 100.0% = design volumetric flow)
Output
eApplicationOpFb
DANFOSS_NOVOCON_APPLICATION_OPERATION
DANFOSS_NOVOCON_APPLICATION_OPERATION.NO_OPERATION
Application operation - feedback
Output
eApplicationComdFb
DANFOSS_NOVOCON_APPLICATION_COMMAND
DANFOSS_NOVOCON_APPLICATION_COMMAND.NO_COMMAND
Application command/status - feedback
Output
eEnergyManagementFb
DANFOSS_NOVOCON_ENERGY_MANAGEMENT
DANFOSS_NOVOCON_ENERGY_MANAGEMENT.NO_MANAGEMENT
Energy management - feedback
Output
eLEDModeFb
DANFOSS_NOVOCON_LED_MODE
DANFOSS_NOVOCON_LED_MODE.NORMAL_MODE
LED mode - feedback
Output
rThermalPower
REAL
Current thermal power (heating power: rPower > 0, cooling power: rPower < 0) in the chosen unit ( eUnitPower)
Output
eUnitThermalPowerFb
DANFOSS_NOVOCON_UNIT_POWER
DANFOSS_NOVOCON_UNIT_POWER.KILOWATT
Unit of thermal power — feedback
Output
rEnergyHeat
REAL
Current heating energy in the chosen unit (eUnitEnergy)
Output
rEnergyCool
REAL
Current cooling energy in the chosen unit (eUnitEnergy)
Output
eUnitEnergyFb
DANFOSS_NOVOCON_UNIT_ENERGY
DANFOSS_NOVOCON_UNIT_ENERGY.KILOWATT_HOURS
Unit of energy — feedback
Output
rAI1
REAL
Actual value at analog input 1 (temperature / resistance) (supply/flow temperature) (use NovoCon Energy cable, NovoCon IO, NovoCon Temperature IO)
Output
rAI2
REAL
Actual value at analog input 2 (temperature / resistance) (return temperature) (use NovoCon Energy cable, NovoCon IO, NovoCon Temperature IO)
Output
rAmountOfWater
REAL
Accumulated amount of water (heating and cooling operation) in liters
Output
sSerialNum
STRING
Device serial number
Output
tRuntimeDriveFb
TIME
TIME#0ms
Runtime of the actuator from 0.0 - 100.0% of the design volumetric flow (in s) — feedback
Output
rAdjustmentRateFb
REAL
0.0
Adjustment rate of the actuator (s/mm) — feedback
Output
rSupplyVoltage
REAL
Current supply voltage of the device in volts
Output
rDeviceTemperature
REAL
Current temperature in the device (unit see register 32790)
Output
rEstimatedLifeSpan
REAL
Calculated percentage of the expected lifespan (100.0%: replace valve and actuator)
Output
xAlarm
BOOL
FALSE
General fault ( TRUE = fault )
Output
xAlarmCom
BOOL
FALSE
General fault - communication ( TRUE = fault )
Output
eErrorCodeCom
ModbusErrorCode
Error code - communication ( 0 = no error )
Output
stErrorCodeDev
STRING
String with the numbers of the active device errors
Output
stWarningCodeDev
STRING
String with the numbers of active device warnings
Output
xBusy
BOOL
Communication indicator ( TRUE = communication )
Input Const
eTempTypeAI1AI2
DANFOSS_NOVOCON_TYPE_AI1AI2
DANFOSS_NOVOCON_TYPE_AI1AI2.PT1000
Type of temperature sensor at analog inputs AI1 and AI2
Input Const
eUnitAI2
DANFOSS_NOVOCON_UNIT_AI1AI2
DANFOSS_NOVOCON_UNIT_AI1AI2.DEGREES_CELSIUS
Unit of AI2
Input Const
eUnitAI1
DANFOSS_NOVOCON_UNIT_AI1AI2
DANFOSS_NOVOCON_UNIT_AI1AI2.DEGREES_CELSIUS
Unit of AI1
Input Const
eLEDMode
DANFOSS_NOVOCON_LED_MODE
DANFOSS_NOVOCON_LED_MODE.NORMAL_MODE
LED operating mode
Input Const
eEnergyManagement
DANFOSS_NOVOCON_ENERGY_MANAGEMENT
DANFOSS_NOVOCON_ENERGY_MANAGEMENT.INACTIVE
Energy management
Input Const
eApplicationOp
DANFOSS_NOVOCON_APPLICATION_OPERATION
DANFOSS_NOVOCON_APPLICATION_OPERATION.DIGITAL_OPERATION
Application operation
Input Const
eUnitActualFlowRate
DANFOSS_NOVOCON_UNIT_ACTUAL_FLOW_RATE
DANFOSS_NOVOCON_UNIT_ACTUAL_FLOW_RATE.LITRES_PER_HOUR
Unit of the actual volumetric flow
Input Const
eUnitSetpFlowRate
DANFOSS_NOVOCON_UNIT_SETP_FLOW_RATE
DANFOSS_NOVOCON_UNIT_SETP_FLOW_RATE.PERCENT
Unit of the volumetric flow setpoint
Input Const
eUnitDesignFlowRate
DANFOSS_NOVOCON_UNIT_DESIGN_FLOW_RATE
DANFOSS_NOVOCON_UNIT_DESIGN_FLOW_RATE.LITRES_PER_HOUR
Unit of the design volumetric flow
Input Const
eValveType
DANFOSS_NOVOCON_VALVE_TYPE
DANFOSS_NOVOCON_VALVE_TYPE.AB_QM_4_0_ISO_DN_15
Valve type Note: On every write to register 33802 (FC06), the volumetric flow setpoint registers 32768/32769, 32796/32797, 32798/32799 and 33024/33025 will be initialized to the nominal values from the 'Valve type selection' table!!!
Input Const
rDesignFlowRateCool
REAL
650.0
Design volumetric flow for cooling mode ( Nominal values: see 'Valve type selection' table)
Input Const
rDesignFlowRateHeat
REAL
650.0
Design volumetric flow for heating mode ( Nominal values: see 'Valve type selection' table)
Input Const
tTimeUpdateInfo
TIME
TIME#0ms
Update interval for the processes influenced by the input ‘xUpdateInfo’
Input Const
tTimeUpdateConfig
TIME
TIME#0ms
Update interval for the processes influenced by the input ‘xUpdateConfig’
Input Const
tTimeUpdateSetp
TIME
TIME#45s0ms
Update interval for operations influenced by the input 'xUpdateSetp'
Input Const
tTimeUpdateActual
TIME
TIME#3s0ms
Update interval for operations influenced by the input 'xUpdateActual'
Last updated

