KNX_Read_DPT_9x

KNX_Read_DPT_9x (FB)

FUNCTION_BLOCK KNX_Read_DPT_9x EXTENDS SlaveBasic

Overview

Read function for DPT 9.x (2-byte floating point number).

Inputs

Inputs
Initial value
Description

xRequest

FALSE

Trigger for single read

xRequestVisu

FALSE

Trigger for single read (visualization)

tRequestTime

T#0S

Interval for cyclic reading

eDPT_Format

-

DPT 9.x format selection

byAdrGroup

0

Group address (0-255)

byAdrMiddleGroup

0

Middle group address (0-7)

byAdrMainGroup

0

Main group address (0-31)

rInitValue

0.0

Initial value at InitOption.InitValue

eInitOption

-

Initialization option

Outputs

  • rValue (REAL): Received floating point value

  • sUnit (STRING[10]): Unit of the value

  • tNextRequest (TIME): Time until next read operation

Usage

  1. Select the DPT 9.x format with eDPT_Format.

  2. Configure the read options as with the previous blocks.

  3. Monitor rValue for received values and sUnit for the unit.

InOut:

Scope
Name
Type
Initial
Comment
Inherited from

Input

itfKnxConnector

IKnxConnector

IMasterConnector interface input to register/unregister the FB to the list on the Master

SlaveBasic

Input

xEnable

BOOL

TRUE

SlaveBasic

Output

sPhysicallAddressDevice

STRING(15)

SlaveBasic

Output

sGroupAddress

STRING(15)

SlaveBasic

Input

xRequest

BOOL

Single Read

Input Const

xRequestVisu

BOOL

Single Read

Input Const

tRequestTime

TIME

TIME#0ms

Monitoring time

Input Const

eDPT_Format

DPT_9x

Enum DPT_9x

Input Const

byAdrGroup

BYTE

0

Group address

Input Const

byAdrMiddleGroup

BYTE

0

Middle group address

Input Const

byAdrMainGroup

BYTE

0

Main group address

Input Const

rInitValue

REAL

Input Const

eInitOption

InitOption

Output

rValue

REAL

Output

sUnit

STRING(10)

Output

tNextRequest

TIME

Last updated