TRANE_SYMBIO_800_RTWF_RTSF
TRANE_SYMBIO_800_RTWF_RTSF (FB)
TRANE_SYMBIO_800_RTWF_RTSF (FB)FUNCTION_BLOCK TRANE_SYMBIO_800_RTWF_RTSF
InOut:
Input
xEn
BOOL
TRUE
Enable / disable of communication ( TRUE = enabled )
Input
byUnitId
BYTE
0
Address of the device
Input
rBASSetpTemp
REAL
7.0
Current setpoint temperature in degrees Celsius ( AI 10100 )
Input
rBASDemLimSetp
REAL
120.0
Current setpoint for the demand limit in percent ( AI 10101 )
Input
xBASReset
BOOL
FALSE
Reset of the unit faults by the supervisory controller (on each rising edge) ( BV 10101 )
Input
rBASMode
REAL
1.0
Functional status of the unit ( 1.0 = Cooling, 2.0 = Heating, 3.0 = Defrost, 4.0 = Free cooling ) ( MV 10100 )
Input
xUpdateActual
BOOL
FALSE
Update of actual values ( on each rising edge )
Input
xUpdateSetp
BOOL
FALSE
Update of setpoints ( on each rising edge )
Input
xResError
BOOL
FALSE
Reinitialization of the outputs ‘eErrorCodeCom’ to the error-free state ( on each rising edge )
Inout
ModbusClient
ModbusClientBase
Client of the device
Output
arrIstwerte_0
ARRAY [10..15] OF REAL
Array for actual values 0 - Registers 10 - 21 - Actual values - Part 1 - Analog Inputs ( FC04 )
Output
arrIstwerte_1
ARRAY [24..29] OF REAL
Array for actual values 1 - Registers 24 - 35 - Actual values - Part 2 - Analog Inputs ( FC04 )
Output
arrIstwerte_2
ARRAY [38..46] OF REAL
Array for actual values 2 - Registers 38 - 55 - Actual values - Part 3 - Analog Inputs ( FC04 )
Output
arrIstwerte_3
ARRAY [58..118] OF REAL
Array for actual values 3 - Registers 58 - 179 - Actual values - Part 4 - Analog Inputs ( FC04 )
Output
arrIstwerte_4
ARRAY [180..185] OF REAL
Array for actual values 4 - Registers 180 - 191 - Actual values - Part 5 - Analog Inputs ( FC04 )
Output
arrIstwerte_5
ARRAY [10..12] OF REAL
Array for actual values 5 - Registers 10 - 15 - Analog Values ( FC03 )
Output
arxIstwerte_6
ARRAY [3010..3045] OF BOOL
Array for actual values 6 - Registers 3010 - 3045 - Binary Inputs ( FC04 )
Output
arxIstwerte_7
ARRAY [3010..3014] OF BOOL
Array for actual values 7 - Registers 3010 - 3014 - Binary Values ( FC03 )
Output
rActSetpTemp
REAL
Current setpoint temperature in degrees Celsius ( AI 10100 )
Output
rActDemLimSetp
REAL
Current setpoint for the demand limit in percent ( AI 10101 )
Output
rEvapEntTemp
REAL
Current evaporator inlet temperature on the chilled water side in degrees Celsius ( AI 10102 )
Output
rEvapLeavTemp
REAL
Current evaporator outlet temperature on the chilled water side in degrees Celsius ( AI 10103 )
Output
rOutsideTemp
REAL
Current outside air temperature in degrees Celsius ( AI 10104 )
Output
rActRunCapacity
REAL
Current running capacity in percent ( AI 10108 )
Output
rCondEntTemp
REAL
Current condenser inlet temperature on the hot water side in degrees Celsius ( AI 10144 )
Output
rCondLeavTemp
REAL
Current condenser outlet temperature on the hot water side in degrees Celsius ( AI 10145 )
Output
rPowerConsumpt
REAL
Current electrical power consumption of the unit in kW ( AI 10146 )
Output
rUnitSourceID
REAL
Current diagnostic code of the unit ( AI 10187 )
Output
rActChiSetpTemp
REAL
Current setpoint temperature - Cooling mode - in degrees Celsius ( AI 10189 )
Output
rActHotSetpTemp
REAL
Current setpoint temperature - Heating mode - in degrees Celsius ( AI 10190 )
Output
xRunEnable
BOOL
Run enable ( FALSE = none, TRUE = active )( BI 10100 )
Output
xChilRunState
BOOL
Primary operating state of the cooling sequence (FALSE = Off, TRUE = On )( BI 10103 )
Output
xEmergencyStop
BOOL
Emergency stop status ( FALSE = Auto, TRUE = Emergency Stop active )( BI 10106 )
Output
xEvaFlowState
BOOL
Chilled water flow status ( FALSE = no flow, TRUE = flow )( BI 10107 )
Output
xDiagShutdwPres
BOOL
Unit shutdown status ( FALSE = Normal, TRUE = Fault )( BI 10109 )
Output
xDiagManResPres
BOOL
Manual reset status of the unit ( FALSE = Normal, TRUE = Fault )( BI 10110 )
Output
xComp1ARunState
BOOL
Operating status of compressor 1A ( FALSE = Stop, TRUE = Auto ) ( BI 10116 )
Output
xComp1BRunState
BOOL
Operating status of compressor 1B ( FALSE = Stop, TRUE = Auto ) ( BI 10117 )
Output
xComp2ARunState
BOOL
Operating status of compressor 2A ( FALSE = Stop, TRUE = Auto ) ( BI 10118 )
Output
xComp2BRunState
BOOL
Operating status of compressor 2B ( FALSE = Stop, TRUE = Auto ) ( BI 10119 )
Output
xExtAutoStop
BOOL
External lockout status of the unit ( FALSE = Stop, TRUE = Auto ) ( BI 10120 )
Output
xCondWaterPump
BOOL
Operating status of the condenser circulation pump in the chilled water circuit ( FALSE = Off, TRUE = On ) ( BI 10121 )
Output
xEvaWaterPump
BOOL
Operating status of the evaporator circulation pump in the hot water circuit ( FALSE = Off, TRUE = On ) ( BI 10122 )
Output
xCondFlowState
BOOL
Hot water flow status ( FALSE = no flow, TRUE = flow )( BI 10123 )
Output
xFrontAutoStop
BOOL
Lockout status of the unit by the local controls at the device ( FALSE = Stop, TRUE = Auto ) ( BI 10124 )
Output
xAlmLatchGen
BOOL
General latched alarm status ( FALSE = Normal, TRUE = Fault ) ( BI 10130 )
Output
xBASAutoStop
BOOL
Lockout status of the unit by the supervisory controller ( FALSE = Stop, TRUE = Auto ) ( BV 10100 )
Output
xBASDiagReset
BOOL
Reset status of the unit faults by the supervisory controller ( FALSE = Normal, TRUE = Reset ) ( BV 10101 )
Output
xBASComp1ALock
BOOL
Lockout status of compressor 1A by the supervisory controller ( FALSE = Normal, TRUE = Lock ) ( BV 10106 )
Output
xBASComp1BLock
BOOL
Lockout status of compressor 1B by the supervisory controller ( FALSE = Normal, TRUE = Lock ) ( BV 10107 )
Output
xBASComp2ALock
BOOL
Lockout status of compressor 2A by the supervisory controller ( FALSE = Normal, TRUE = Lock ) ( BV 10108 )
Output
xBASComp2BLock
BOOL
Lockout status of compressor 2B by the supervisory controller ( FALSE = Normal, TRUE = Lock ) ( BV 10109 )
Output
xBASEvaWaterPump
BOOL
Request status of the evaporator circulation pump in the hot water circuit by the supervisory controller ( FALSE = Auto, TRUE = On ) ( BV 10110 )
Output
xBASConWaterPump
BOOL
Request status of the condenser circulation pump in the chilled water circuit by the supervisory controller ( FALSE = Auto, TRUE = On ) ( BV 10111 )
Output
rRunMode
REAL
Operating status of the unit ( 1.0 = Off, 2.0 = Start, 3.0 = Run, 4.0 = Pre-Shutdown, 5.0 = Service, information not saved ) ( MI 10100 )
Output
rOperatingMode
REAL
Functional status of the unit ( 1.0 = Cooling, 2.0 = Heating, 3.0 = Defrost, 4.0 = Free cooling ) ( MI 10101 )
Output
rBASOperatMode
REAL
Functional status of the unit by the supervisory controller ( 1.0 = Cooling, 2.0 = Heating, 3.0 = Defrost, 4.0 = Free cooling ) ( MV 10100 )
Output
xAlarm
BOOL
FALSE
Collective fault ( TRUE = fault )
Output
xAlarmCom
BOOL
FALSE
Collective fault - communication ( TRUE = fault )
Output
eErrorCodeCom
ModbusErrorCode
Error code - communication ( 0 = no error )
Output
xBusy
BOOL
Communication indicator ( TRUE = communication )
Input Const
diAdrOffset
DINT
0
Offset for calculating Modbus addresses ( from the Modbus registers ) ( Permissible range: -1, 0, +1 )
Input Const
tTimeUpdateSetp
TIME
TIME#45s0ms
Update interval for the processes affected by the input ‘xUpdateSetp’
Input Const
tTimeUpdateActual
TIME
TIME#10s0ms
Update interval for the processes affected by the input ‘xUpdateActual’
Last updated

