TRANE_SYMBIO_800_RTWF_RTSF

TRANE_SYMBIO_800_RTWF_RTSF (FB)

FUNCTION_BLOCK TRANE_SYMBIO_800_RTWF_RTSF

Representation

InOut:

Scope
Name
Type
Initial
Comment

Input

xEn

BOOL

TRUE

Enable / disable communication (TRUE = enable)

Input

byUnitId

BYTE

0

Device address

Input

rBASSetpTemp

REAL

7.0

Current setpoint temperature in degrees Celsius (AI 10100)

Input

rBASDemLimSetp

REAL

120.0

Current setpoint for the demand limit in percent ( AI 10101)

Input

xBASReset

BOOL

FALSE

Reset of the unit faults by the higher-level controller (on each rising edge) (BV 10101)

Input

rBASMode

REAL

1.0

Operating status of the unit (1.0 = Cooling, 2.0 = Heating, 3.0 = Defrost, 4.0 = Free Cooling) (MV 10100)

Input

xUpdateActual

BOOL

FALSE

Update of actual values (on every rising edge )

Input

xUpdateSetp

BOOL

FALSE

Update of setpoints (on every rising edge )

Input

xResError

BOOL

FALSE

Reinitialization of the outputs eErrorCodeCom in the fault-free state (on each rising edge)

Inout

ModbusClient

ModbusClientBase

Client of the device

Output

arrIstwerte_0

ARRAY [10 .. 15] OF REAL

Array for actual values 0 - Register 10 - 21 - Actual values - Part 1 - Analog Inputs (FC04)

Output

arrIstwerte_1

ARRAY [24 .. 29] OF REAL

Array for actual values 1 - Register 24 - 35 - Actual values - Part 2 - Analog Inputs (FC04)

Output

arrIstwerte_2

ARRAY [38 .. 46] OF REAL

Array for actual values 2 - Register 38 - 55 - Actual values - Part 3 - Analog Inputs (FC04)

Output

arrIstwerte_3

ARRAY [58 .. 118] OF REAL

Array for actual values 3 - Register 58 - 179 - Actual values - Part 4 - Analog Inputs (FC04)

Output

arrIstwerte_4

ARRAY [180 .. 185] OF REAL

Array for actual values 4 - Register 180 - 191 - Actual values - Part 5 - Analog Inputs (FC04)

Output

arrIstwerte_5

ARRAY [10 .. 12] OF REAL

Array for actual values 5 - Register 10 - 15 - Analog Values (FC03)

Output

arxIstwerte_6

ARRAY [3010 .. 3045] OF BOOL

Array for actual values 6 - Register 3010 - 3045 - Binary Inputs (FC04)

Output

arxIstwerte_7

ARRAY [3010 .. 3014] OF BOOL

Array for actual values 7 - Register 3010 - 3014 - Binary Values (FC03)

Output

rActSetpTemp

REAL

Current setpoint temperature in degrees Celsius (AI 10100)

Output

rActDemLimSetp

REAL

Current setpoint for the demand limit in percent ( AI 10101)

Output

rEvapEntTemp

REAL

Current chilled-water inlet temperature in degrees Celsius (AI 10102)

Output

rEvapLeavTemp

REAL

Current chilled-water outlet temperature in degrees Celsius (AI 10103)

Output

rOutsideTemp

REAL

Current outdoor temperature in degrees Celsius (AI 10104)

Output

rActRunCapacity

REAL

Current operating capacity in percent (AI 10108)

Output

rCondEntTemp

REAL

Current hot-water inlet temperature in degrees Celsius (AI 10144)

Output

rCondLeavTemp

REAL

Current hot-water outlet temperature in degrees Celsius (AI 10145)

Output

rPowerConsumpt

REAL

Current electrical power consumption of the unit in kW (AI 10146)

Output

rUnitSourceID

REAL

Current diagnostic code of the unit (AI 10187)

Output

rActChiSetpTemp

REAL

Current setpoint temperature - cooling mode - in degrees Celsius ( AI 10189)

Output

rActHotSetpTemp

REAL

Current setpoint temperature - heating mode - in degrees Celsius ( AI 10190)

Output

xRunEnable

BOOL

Operating readiness (FALSE = none, TRUE = active)(BI 10100)

Output

xChilRunState

BOOL

Primary operating mode of the cooling sequence (FALSE = Off, TRUE = On )(BI 10103)

Output

xEmergencyStop

BOOL

Status of the emergency stop (FALSE = Auto, TRUE = emergency stop active)( BI 10106)

Output

xEvaFlowState

BOOL

Status of chilled water flow (FALSE = no flow, TRUE = flow)(BI 10107)

Output

xDiagShutdwPres

BOOL

Status of the unit shutdown (FALSE = Normal, TRUE = fault)(BI 10109)

Output

xDiagManResPres

BOOL

Status of the manual reset of the unit (FALSE = Normal, TRUE = fault)(BI 10110)

Output

xComp1ARunState

BOOL

Operating status of compressor 1A (FALSE = Stop, TRUE = Auto) (BI 10116)

Output

xComp1BRunState

BOOL

Operating status of compressor 1B (FALSE = Stop, TRUE = Auto) (BI 10117)

Output

xComp2ARunState

BOOL

Operating status of compressor 2A (FALSE = Stop, TRUE = Auto) (BI 10118)

Output

xComp2BRunState

BOOL

Operating status of compressor 2B (FALSE = Stop, TRUE = Auto) (BI 10119)

Output

xExtAutoStop

BOOL

Status of the external lockout of the unit (FALSE = Stop, TRUE = Auto) (BI 10120)

Output

xCondWaterPump

BOOL

Status of operation of the circulation pump in the chilled-water circuit ( FALSE = Off, TRUE = On) (BI 10121)

Output

xEvaWaterPump

BOOL

Status of operation of the circulation pump in the hot-water circuit ( FALSE = Off, TRUE = On) (BI 10122)

Output

xCondFlowState

BOOL

Status of hot water flow (FALSE = no flow, TRUE = flow)(BI 10123)

Output

xFrontAutoStop

BOOL

Status of the unit lockout via the device panel (FALSE = Stop, TRUE = Auto) (BI 10124)

Output

xAlmLatchGen

BOOL

Status of the general latched alarm (FALSE = Normal, TRUE = fault) (BI 10130)

Output

xBASAutoStop

BOOL

Status of the unit lockout by the higher-level controller (FALSE = Stop, TRUE = Auto) (BV 10100)

Output

xBASDiagReset

BOOL

Status of the reset of the unit faults by the higher-level controller (FALSE = Normal, TRUE = Reset) ( BV 10101)

Output

xBASComp1ALock

BOOL

Status of the shutdown of compressor 1A by the higher-level controller (FALSE = Normal, TRUE = lockout) (BV 10106)

Output

xBASComp1BLock

BOOL

Status of the shutdown of compressor 1B by the higher-level controller (FALSE = Normal, TRUE = lockout) (BV 10107)

Output

xBASComp2ALock

BOOL

Status of the shutdown of compressor 2A by the higher-level controller (FALSE = Normal, TRUE = lockout) (BV 10108)

Output

xBASComp2BLock

BOOL

Status of the shutdown of compressor 2B by the higher-level controller (FALSE = Normal, TRUE = lockout) (BV 10109)

Output

xBASEvaWaterPump

BOOL

Status of the request for the circulation pump in the hot-water circuit by the higher-level controller (FALSE = Auto, TRUE = On ) (BV 10110)

Output

xBASConWaterPump

BOOL

Status of the request for the circulation pump in the chilled-water circuit by the higher-level controller (FALSE = Auto, TRUE = On ) (BV 10111)

Output

rRunMode

REAL

Operating status of the unit (1.0 = Off, 2.0 = Start, 3.0 = Run, 4.0 = Pre-Shutdown, 5.0 = Service, information not saved) (MI 10100)

Output

rOperatingMode

REAL

Operating status of the unit (1.0 = Cooling, 2.0 = Heating, 3.0 = Defrost, 4.0 = Free Cooling) (MI 10101)

Output

rBASOperatMode

REAL

Operating status of the unit by the higher-level controller (1.0 = Cooling, 2.0 = Heating, 3.0 = Defrost, 4.0 = Free Cooling) (MV 10100)

Output

xAlarm

BOOL

FALSE

Collective fault (TRUE = fault)

Output

xAlarmCom

BOOL

FALSE

Collective fault - communication (TRUE = fault)

Output

eErrorCodeCom

ModbusErrorCode

Error code - communication (0 = no error)

Output

xBusy

BOOL

Communication indicator (TRUE = communication)

Input Const

diAdrOffset

DINT

0

Offset for calculating the Modbus addresses (from the Modbus registers) (permitted range: -1, 0, +1)

Input Const

tTimeUpdateSetp

TIME

TIME#45s0ms

Update interval for the processes influenced by the input xUpdateSetp influenced

Input Const

tTimeUpdateActual

TIME

TIME#10s0ms

Update interval for the processes influenced by the input xUpdateActual influenced

Last updated