TRANE_SYMBIO_800_RTWF_RTSF
TRANE_SYMBIO_800_RTWF_RTSF (FB)
TRANE_SYMBIO_800_RTWF_RTSF (FB)FUNCTION_BLOCK TRANE_SYMBIO_800_RTWF_RTSF
Representation

InOut:
Input
xEn
BOOL
TRUE
Enable / disable communication (TRUE = enable)
Input
byUnitId
BYTE
0
Device address
Input
rBASSetpTemp
REAL
7.0
Current setpoint temperature in degrees Celsius (AI 10100)
Input
rBASDemLimSetp
REAL
120.0
Current setpoint for the demand limit in percent ( AI 10101)
Input
xBASReset
BOOL
FALSE
Reset of the unit faults by the higher-level controller (on each rising edge) (BV 10101)
Input
rBASMode
REAL
1.0
Operating status of the unit (1.0 = Cooling, 2.0 = Heating, 3.0 = Defrost, 4.0 = Free Cooling) (MV 10100)
Input
xUpdateActual
BOOL
FALSE
Update of actual values (on every rising edge )
Input
xUpdateSetp
BOOL
FALSE
Update of setpoints (on every rising edge )
Input
xResError
BOOL
FALSE
Reinitialization of the outputs eErrorCodeCom in the
fault-free state (on each rising edge)
Inout
ModbusClient
ModbusClientBase
Client of the device
Output
arrIstwerte_0
ARRAY [10 .. 15] OF REAL
Array for actual values 0 - Register 10 - 21 - Actual values - Part 1 - Analog Inputs (FC04)
Output
arrIstwerte_1
ARRAY [24 .. 29] OF REAL
Array for actual values 1 - Register 24 - 35 - Actual values - Part 2 - Analog Inputs (FC04)
Output
arrIstwerte_2
ARRAY [38 .. 46] OF REAL
Array for actual values 2 - Register 38 - 55 - Actual values - Part 3 - Analog Inputs (FC04)
Output
arrIstwerte_3
ARRAY [58 .. 118] OF REAL
Array for actual values 3 - Register 58 - 179 - Actual values - Part 4 - Analog Inputs (FC04)
Output
arrIstwerte_4
ARRAY [180 .. 185] OF REAL
Array for actual values 4 - Register 180 - 191 - Actual values - Part 5 - Analog Inputs (FC04)
Output
arrIstwerte_5
ARRAY [10 .. 12] OF REAL
Array for actual values 5 - Register 10 - 15 - Analog Values (FC03)
Output
arxIstwerte_6
ARRAY [3010 .. 3045] OF
BOOL
Array for actual values 6 - Register 3010 - 3045 - Binary Inputs (FC04)
Output
arxIstwerte_7
ARRAY [3010 .. 3014] OF
BOOL
Array for actual values 7 - Register 3010 - 3014 - Binary Values (FC03)
Output
rActSetpTemp
REAL
Current setpoint temperature in degrees Celsius (AI 10100)
Output
rActDemLimSetp
REAL
Current setpoint for the demand limit in percent ( AI 10101)
Output
rEvapEntTemp
REAL
Current chilled-water inlet temperature in degrees Celsius (AI 10102)
Output
rEvapLeavTemp
REAL
Current chilled-water outlet temperature in degrees Celsius (AI 10103)
Output
rOutsideTemp
REAL
Current outdoor temperature in degrees Celsius (AI 10104)
Output
rActRunCapacity
REAL
Current operating capacity in percent (AI 10108)
Output
rCondEntTemp
REAL
Current hot-water inlet temperature in degrees Celsius (AI 10144)
Output
rCondLeavTemp
REAL
Current hot-water outlet temperature in degrees Celsius (AI 10145)
Output
rPowerConsumpt
REAL
Current electrical power consumption of the unit in kW (AI 10146)
Output
rUnitSourceID
REAL
Current diagnostic code of the unit (AI 10187)
Output
rActChiSetpTemp
REAL
Current setpoint temperature - cooling mode - in degrees Celsius ( AI 10189)
Output
rActHotSetpTemp
REAL
Current setpoint temperature - heating mode - in degrees Celsius ( AI 10190)
Output
xRunEnable
BOOL
Operating readiness (FALSE = none, TRUE = active)(BI 10100)
Output
xChilRunState
BOOL
Primary operating mode of the cooling sequence (FALSE = Off, TRUE = On )(BI 10103)
Output
xEmergencyStop
BOOL
Status of the emergency stop (FALSE = Auto, TRUE = emergency stop active)( BI 10106)
Output
xEvaFlowState
BOOL
Status of chilled water flow (FALSE = no flow, TRUE = flow)(BI 10107)
Output
xDiagShutdwPres
BOOL
Status of the unit shutdown (FALSE = Normal, TRUE = fault)(BI 10109)
Output
xDiagManResPres
BOOL
Status of the manual reset of the unit (FALSE = Normal, TRUE = fault)(BI 10110)
Output
xComp1ARunState
BOOL
Operating status of compressor 1A (FALSE = Stop, TRUE = Auto) (BI 10116)
Output
xComp1BRunState
BOOL
Operating status of compressor 1B (FALSE = Stop, TRUE = Auto) (BI 10117)
Output
xComp2ARunState
BOOL
Operating status of compressor 2A (FALSE = Stop, TRUE = Auto) (BI 10118)
Output
xComp2BRunState
BOOL
Operating status of compressor 2B (FALSE = Stop, TRUE = Auto) (BI 10119)
Output
xExtAutoStop
BOOL
Status of the external lockout of the unit (FALSE = Stop, TRUE = Auto) (BI 10120)
Output
xCondWaterPump
BOOL
Status of operation of the circulation pump in the chilled-water circuit ( FALSE = Off, TRUE = On) (BI 10121)
Output
xEvaWaterPump
BOOL
Status of operation of the circulation pump in the hot-water circuit ( FALSE = Off, TRUE = On) (BI 10122)
Output
xCondFlowState
BOOL
Status of hot water flow (FALSE = no flow, TRUE = flow)(BI 10123)
Output
xFrontAutoStop
BOOL
Status of the unit lockout via the device panel (FALSE = Stop, TRUE = Auto) (BI 10124)
Output
xAlmLatchGen
BOOL
Status of the general latched alarm (FALSE = Normal, TRUE = fault) (BI 10130)
Output
xBASAutoStop
BOOL
Status of the unit lockout by the higher-level controller (FALSE = Stop, TRUE = Auto) (BV 10100)
Output
xBASDiagReset
BOOL
Status of the reset of the unit faults by the higher-level controller (FALSE = Normal, TRUE = Reset) ( BV 10101)
Output
xBASComp1ALock
BOOL
Status of the shutdown of compressor 1A by the higher-level controller (FALSE = Normal, TRUE = lockout) (BV 10106)
Output
xBASComp1BLock
BOOL
Status of the shutdown of compressor 1B by the higher-level controller (FALSE = Normal, TRUE = lockout) (BV 10107)
Output
xBASComp2ALock
BOOL
Status of the shutdown of compressor 2A by the higher-level controller (FALSE = Normal, TRUE = lockout) (BV 10108)
Output
xBASComp2BLock
BOOL
Status of the shutdown of compressor 2B by the higher-level controller (FALSE = Normal, TRUE = lockout) (BV 10109)
Output
xBASEvaWaterPump
BOOL
Status of the request for the circulation pump in the hot-water circuit by the higher-level controller (FALSE = Auto, TRUE = On ) (BV 10110)
Output
xBASConWaterPump
BOOL
Status of the request for the circulation pump in the chilled-water circuit by the higher-level controller (FALSE = Auto, TRUE = On ) (BV 10111)
Output
rRunMode
REAL
Operating status of the unit (1.0 = Off, 2.0 = Start, 3.0 = Run, 4.0 = Pre-Shutdown, 5.0 = Service, information not saved) (MI 10100)
Output
rOperatingMode
REAL
Operating status of the unit (1.0 = Cooling, 2.0 = Heating, 3.0 = Defrost, 4.0 = Free Cooling) (MI 10101)
Output
rBASOperatMode
REAL
Operating status of the unit by the higher-level controller (1.0 = Cooling, 2.0 = Heating, 3.0 = Defrost, 4.0 = Free Cooling) (MV 10100)
Output
xAlarm
BOOL
FALSE
Collective fault (TRUE = fault)
Output
xAlarmCom
BOOL
FALSE
Collective fault - communication (TRUE = fault)
Output
eErrorCodeCom
ModbusErrorCode
Error code - communication (0 = no error)
Output
xBusy
BOOL
Communication indicator (TRUE = communication)
Input Const
diAdrOffset
DINT
0
Offset for calculating the Modbus addresses (from the Modbus registers) (permitted range: -1, 0, +1)
Input Const
tTimeUpdateSetp
TIME
TIME#45s0ms
Update interval for the processes influenced by the input
xUpdateSetp influenced
Input Const
tTimeUpdateActual
TIME
TIME#10s0ms
Update interval for the processes influenced by the input
xUpdateActual influenced
Last updated

