SYSTEMAIR_ACCESS_CONTROL
SYSTEMAIR_ACCESS_CONTROL (FB)
SYSTEMAIR_ACCESS_CONTROL (FB)FUNCTION_BLOCK SYSTEMAIR_ACCESS_CONTROL
InOut:
Input
xEn
BOOL
TRUE
Enable / disable of communication ( TRUE = enabled )
Input
byUnitId
BYTE
0
Address of the device
Input
xUpdateActual
BOOL
FALSE
Update of actual values ( on each rising edge )
Input
xUpdateSetp
BOOL
FALSE
Update of setpoints ( on each rising edge )
Input
eExternalCon
SYSTEMAIR_ACCESS_CONTROL_EXTERNAL_CONTROL
SYSTEMAIR_ACCESS_CONTROL_EXTERNAL_CONTROL.NO_EXTERNAL_CONTROL
External control of the unit — default
Input
eTempConMode
SYSTEMAIR_ACCESS_CONTROL_TEMP_CONTR_MODE
SYSTEMAIR_ACCESS_CONTROL_TEMP_CONTR_MODE.SUPPLY_AIR
Type of temperature control of the unit — default
Input
eFanConMode
SYSTEMAIR_ACCESS_CONTROL_FAN_CONT_MODE
SYSTEMAIR_ACCESS_CONTROL_FAN_CONT_MODE.FLOW
Type of fan control of the unit — default
Input
rSpTempSupplyAir
REAL
21.0
Supply air setpoint temperature in degrees Celsius when eTempConMode = SYSTEMAIR_ACCESS_CONTROL_TEMP_CONTR_MODE.SUPPLY_AIR
Input
rSpTempExtrAir
REAL
22.0
Exhaust air setpoint temperature in degrees Celsius when eTempConMode = SYSTEMAIR_ACCESS_CONTROL_TEMP_CONTR_MODE.EXTRACT_AIR_CASCADE
Input
rSpTempRoom
REAL
22.0
Room setpoint temperature in degrees Celsius when eTempConMode = SYSTEMAIR_ACCESS_CONTROL_TEMP_CONTR_MODE.ROOM_CASCADE
Input
xAckAlarmsDev
BOOL
FALSE
Acknowledge all alarms ( TRUE = active )
Input
xResAlarmSICDev
BOOL
FALSE
Reset of the service interval counter alarm ( TRUE = active )
Input
xResError
BOOL
FALSE
Reinitialization of the output 'eErrorCodeCom' to the error-free state (on each rising edge)
Inout
ModbusClient
ModbusClientBase
Client of the device
Output
eUnitModeFb
SYSTEMAIR_ACCESS_CONTROL_OP_MODE_FB
Operating mode of the unit — feedback
Output
eUnitTrigFb
SYSTEMAIR_ACCESS_CONTROL_TRIG_FB
Cause of the unit's current operating mode — feedback
Output
eExternalConFB
SYSTEMAIR_ACCESS_CONTROL_EXTERNAL_CONTROL
State of the unit's external control — feedback
Output
eTempConModeFB
SYSTEMAIR_ACCESS_CONTROL_TEMP_CONTR_MODE
Current type of temperature control of the unit — feedback
Output
eFanConModeFB
SYSTEMAIR_ACCESS_CONTROL_FAN_CONT_MODE
Current type of fan control of the unit — feedback
Output
eSupAirFanMode
SYSTEMAIR_ACCESS_CONTROL_FAN_MODE
Operating mode of the supply air fan
Output
eExtAirFanMode
SYSTEMAIR_ACCESS_CONTROL_FAN_MODE
Operating mode of the extract air fan
Output
rTempOda
REAL
Current outside temperature in degrees Celsius
Output
rTempIntakeAir
REAL
Current intake air temperature in degrees Celsius
Output
rTempSupplyAir
REAL
Current supply air temperature in degrees Celsius
Output
rTempExhaustAir
REAL
Current exhaust air temperature in degrees Celsius
Output
rTempExtractAir
REAL
Current extract air temperature in degrees Celsius
Output
rSupplyAirPres
REAL
Current pressure in the supply air in Pa
Output
rExtractAirPres
REAL
Current pressure in the extract air in Pa
Output
rSupplyAirFlow
REAL
Current volumetric flow in the supply air
Output
rExtractAirFlow
REAL
Current volumetric flow in the extract air
Output
rExtractAirCO2
REAL
Current CO2 concentration in the extract air / room in ppm
Output
rExtractAirHum
REAL
Current relative humidity in the extract air / room in percent
Output
rFilterSupAir
REAL
Differential pressure - filter - supply air in Pa
Output
rFilterExtAir
REAL
Differential pressure - filter - extract air in Pa
Output
rTempAveragRoom
REAL
Temperature - average of all four room temperature sensors in degrees Celsius
Output
rActiveSeq
REAL
Number of the active sequence ( 1 … 10 )
Output
arrContSigSeq
ARRAY [1..10] OF REAL
Control signal of the individual sequences ( 1 … 10 )
Output
rSupAirFanCon
REAL
Control signal for the supply air fan in percent
Output
rExtAirFanCon
REAL
Control signal for the extract air fan in percent
Output
rSpTempSupplyAirFb
REAL
Current setpoint of the supply air temperature in degrees Celsius — feedback
Output
rSpSupAirFan
REAL
Current setpoint for the supply air fan as pressure / volumetric flow
Output
rSpExtAirFan
REAL
Current setpoint for the extract air fan as pressure / volumetric flow
Output
rSFP
REAL
Specific fan power in Ws/m3
Output
rSupAirFanUpM
REAL
Rotational speed of the supply air fan in revolutions per minute
Output
rExtAirFanUpM
REAL
Rotational speed of the extract air fan in revolutions per minute
Output
rPosDamper_1
REAL
Current position of damper 1 in percent
Output
rPosDamper_2
REAL
Current position of damper 2 in percent
Output
rPosDamper_3
REAL
Current position of damper 3 in percent
Output
rPosDamper_4
REAL
Current position of damper 4 in percent
Output
rPosDamper_5
REAL
Current position of damper 5 in percent
Output
rSpSupAirCool
REAL
Setpoint - supply air temperature in cooling mode in degrees Celsius
Output
rSpSupAirHeat
REAL
Setpoint - supply air temperature in heating mode in degrees Celsius
Output
rSpDehum
REAL
Setpoint - dehumidification in percent relative humidity
Output
rSpHum
REAL
Setpoint - humidification in percent relative humidity
Output
eHumConMode
SYSTEMAIR_ACCESS_CONTROL_HUM_MODE
Current operating mode for humidification / dehumidification
Output
xErrorDevice_A
BOOL
Alarm output - unacknowledged fault messages - Alarm A ( TRUE = fault active )
Output
xErrorDevice_B
BOOL
Alarm output - unacknowledged fault messages - Alarm B ( TRUE = fault active )
Output
xErrorDevice_C
BOOL
Alarm output - unacknowledged fault messages - Alarm C ( TRUE = fault active )
Output
xFilterSupAir
BOOL
Filter maintenance indicator - supply air ( TRUE = maintenance required )
Output
xFilterExtAir
BOOL
Filter maintenance indicator - extract air ( TRUE = maintenance required )
Output
xFireAlarm
BOOL
Fire alarm ( TRUE = alarm active )
Output
xSmokeAlarm
BOOL
Smoke alarm ( TRUE = alarm active )
Output
xAlarm
BOOL
FALSE
Collective fault ( TRUE = fault )
Output
xAlarmCom
BOOL
FALSE
Collective fault - communication ( TRUE = fault )
Output
eErrorCodeCom
ModbusErrorCode
Error code - communication ( 0 = no error )
Output
xBusy
BOOL
Communication indicator ( TRUE = communication )
Input Const
diAdrOffset
DINT
0
Offset for calculating Modbus addresses ( from the Modbus registers ) ( Permissible range: -1, 0, +1 )
Input Const
tTimeUpdateSetp
TIME
TIME#45s0ms
Update interval for the processes affected by the input ‘xUpdateSetp’
Input Const
tTimeUpdateActual
TIME
TIME#10s0ms
Update interval for the processes affected by the input ‘xUpdateActual’
Last updated

