PRIGNITZ_CIT2
PRIGNITZ_CIT2 (FB)
PRIGNITZ_CIT2 (FB)FUNCTION_BLOCK PRIGNITZ_CIT2
InOut:
Input
xEn
BOOL
TRUE
Enable / disable of communication ( TRUE = enabled )
Input
byUnitId
BYTE
0
Address of the device
Input
xUpdateActual
BOOL
FALSE
Update of actual values ( on each rising edge )
Input
xUpdateInfo
BOOL
FALSE
Update of device information (on each rising edge)
Inout
ModbusClient
ModbusClientBase
Client of the device
Output
rPressureDigit
REAL
Pressure actual value in digits (0 … 10000)
Output
rPressureUnit
REAL
Pressure actual value in the unit of measurement
Output
rTemperature
REAL
Temperature in degrees Celsius
Output
rRangeUnit
REAL
Measuring range in the unit of measurement
Output
rRangeDigit
REAL
Measuring range in digits
Output
rRiseUnit
REAL
Rise in the unit of measurement
Output
rPressureMinUnit
REAL
Minimum value - measuring range in the unit of measurement
Output
rPressureMaxUnit
REAL
Maximum value - measuring range in the unit of measurement
Output
sUnit
STRING
Unit of measurement
Output
xSensorOffsetInDevice
BOOL
Indicates whether sensor calibration must be performed in the device (TRUE = calibration required in device, FALSE = calibration in FB required)
Output
wSerialNum_H
WORD
Device serial number - part H (printed on the sensor in HEX format)
Output
wSerialNum_M
WORD
Device serial number - part M (printed on the sensor in HEX format)
Output
wSerialNum_L
WORD
Device serial number - part L (printed on the sensor in HEX format)
Output
wSerialNum_X
WORD
Device serial number - part X (printed on the sensor in HEX format)
Output
xAlarm
BOOL
FALSE
Collective fault ( TRUE = fault )
Output
xAlarmCom
BOOL
FALSE
Collective fault - communication ( TRUE = fault )
Output
eErrorCodeCom
ModbusErrorCode
Error code - communication ( 0 = no error )
Output
xBusy
BOOL
Communication indicator ( TRUE = communication )
Input Const
rTemperatureOffset
REAL
0.0
Constant measurement offset for the transmitted temperature - actual value
Input Const
rPressureUnitOffset
REAL
0.0
Constant measurement value offset for the transmitted pressure - actual value
Input Const
diAdrOffset
DINT
0
Offset for calculating Modbus addresses ( from the Modbus registers ) ( Permissible range: -1, 0, +1 )
Input Const
tTimeUpdateActual
TIME
TIME#3s0ms
Update interval for the processes affected by the input ‘xUpdateActual’
Last updated

