HELIOS_KWL_MODBUS_GATEWAY
HELIOS_KWL_MODBUS_GATEWAY (FB)
HELIOS_KWL_MODBUS_GATEWAY (FB)FUNCTION_BLOCK HELIOS_KWL_MODBUS_GATEWAY
Representation

InOut:
Input
xEn
BOOL
TRUE
Enable / disable of communication ( TRUE = enabled )
Input
byUnitId
BYTE
180
Address of the device
Input
rSetpFanStage
REAL
0.0
Setpoint - fan stage (0 - 4, 0 = off)
Input
rSetpTemp
REAL
21.0
Setpoint - comfort temperature
Input
xResError
BOOL
FALSE
Reinitialization of the output ‘eErrorCodeCom’ to the error-free state (on each rising edge)
Input
xUpdateActual
BOOL
FALSE
Update of actual values ( on every rising edge )
Input
xUpdateSetp
BOOL
FALSE
Update of setpoint values ( on every rising edge )
Inout
ModbusClient
ModbusClientBase
Client of the device
Output
rErrorCount
REAL
Number of active errors (0 - 32)
Output
rWarnCount
REAL
Number of active warnings (0 - 8)
Output
rSetpFanStage_Fb
REAL
Currently active fan stage (0 - 4, 0 = off)
Output
xChangeFilter
BOOL
1 = filter maintenance required
Output
xOP
BOOL
1 = ventilation operating
Output
rSetpTemp_Fb
REAL
Feedback - setpoint - comfort temperature
Output
xAlarm
BOOL
FALSE
Collective fault ( TRUE = Fault )
Output
xAlarmCom
BOOL
FALSE
Collective fault - communication ( TRUE = Fault )
Output
eErrorCodeCom
ModbusErrorCode
Error code - communication ( 0 = no error )
Output
xAlarmDevice
BOOL
FALSE
Aggregate fault - device (TRUE = fault)
Output
eErrorCodeDev
HELIOS_KWL_MODBUS_GATEWAY_ERROR_CODE
HELIOS_KWL_MODBUS_GATEWAY_ERROR_CODE.NO_ERROR
Error code - device (0 = no error)
Output
xBusy
BOOL
Communication indicator ( TRUE = Communication )
Input Const
rSetpFanStageMin
REAL
0.0
Currently active minimum fan stage (0 - 1, 0 = switching off via fan stage possible)
Input Const
tTimeUpdateSetp
TIME
TIME#45s0ms
Update interval for the operations influenced by the input ‘xUpdateSetp’
Input Const
tTimeUpdateActual
TIME
TIME#3s0ms
Update interval for the operations influenced by the input ‘xUpdateActual’
Last updated

