GRUNDFOS_MAGNA_3_MONO
GRUNDFOS_MAGNA_3_MONO (FB)
GRUNDFOS_MAGNA_3_MONO (FB)FUNCTION_BLOCK GRUNDFOS_MAGNA_3_MONO
Representation

InOut:
Input
xEn
BOOL
TRUE
Enable / disable of communication ( TRUE = enabled )
Input
byUnitId
BYTE
0
Device address ( 1 .. 247 )
Input
xUpdateActual
BOOL
FALSE
Update of actual values ( on every rising edge )
Input
xUpdateSetp
BOOL
FALSE
Update of setpoint values ( on every rising edge )
Input
xEnPump
BOOL
FALSE
Enable / disable the pump (FALSE = Off, TRUE = On)
Input
xOverride_Max
BOOL
FALSE
Enable / disable the override - maximum operation ( FALSE = Off, TRUE = On)
Input
xOverride_Min
BOOL
FALSE
Enable / disable the override - minimum operation ( FALSE = Off, TRUE = On)
Input
xResErrorWarn
BOOL
FALSE
Signal to reset alarms / warnings (rising edge)
Input
rSetp
REAL
0.0
Setpoint - pump (unit/value range depending on operating mode )
Inout
ModbusClient
ModbusClientBase
Client of the device
Output
eForceModeFb
Grundfos_OperationMode
Current pump operating mode (forced control)
Output
eOperationModeFb
Grundfos_ControlStatFb
Current pump operating mode (control / regulation)
Output
wOperationStatFb
WORD
Current operating status
Output
xOperation
BOOL
Current pump operation message (FALSE = Off)
Output
rSetpFb
REAL
Feedback of the current setpoint in XXX.XX percent
Output
rProcessFb
REAL
Measured value of the controlled variable in percent
Output
rRelativePerfor
REAL
Current relative load in XXX.XX percent
Output
rSpeed
REAL
Current pump speed in XXX rpm
Output
xMaxSpeed
BOOL
Pump running at maximum speed (TRUE = On)
Output
xMinSpeed
BOOL
Pump running at minimum speed (TRUE = On)
Output
rFrequency
REAL
Current frequency of the VFD in XX.X Hz
Output
rPressure
REAL
Current pressure measured value in XX.XXX bar
Output
rDiffPressure
REAL
Current differential pressure measured value (inlet, outlet) in XX.XXX bar
Output
rRemotePressure1
REAL
Current external pressure measured value 1 in XX.XXX bar
Output
rFlow
REAL
Current volumetric flow in XX.X m3/h
Output
rFluidTemp
REAL
Current temperature in the medium in XXX.XX degrees Celsius
Output
rRemoteTemp2
REAL
Current external temperature 2 in XXX.XX degrees Celsius
Output
xSensorOffsetInDevice
BOOL
Indicates whether the sensor calibration must be performed in the device ( TRUE = calibration required in device, FALSE = calibration required in FB )
Output
rElecCurrent
REAL
Current electrical input current in XX.X A
Output
rDCVoltage
REAL
Current DC link voltage in XXX.X V
Output
dwElecPower
DWORD
Current electrical input power in XXX W
Output
rElectronicTemp
REAL
Current temperature of the electronics in XXX.XX degrees Celsius
Output
dwOperatingHours
DWORD
Current number of operating hours in XXX h
Output
dwElecEnergyTotal
DWORD
Total consumed electrical energy in XXX kWh#
Output
dwNumberOfStarts
DWORD
Current number of starts
Output
rDiffTemp
REAL
Current temperature difference (supply temperature - return temperature) in Kelvin
Output
dwPowerHeating
DWORD
Current heat output in the heating circuit in XXX W
Output
dwHeatEnergyTotal
DWORD
Total heat energy in XXX kWh (non-resettable)
Output
dwHeatVolumeTotal
DWORD
Total water volume in heating operation in XXX.XX m3 (non- resettable)
Output
dwCoolEnergyTotal
DWORD
Total cooling energy in XXX kWh (non-resettable)
Output
dwCoolVolumeTotal
DWORD
Total water volume in cooling operation in XXX.XX m3 (non- resettable)
Output
xAccessMode
BOOL
Current source for operation (TRUE = REMOTE = MODBUS)
Output
xWarningDevice
BOOL
Collective warning - device (TRUE = warning)
Output
xAlarm
BOOL
FALSE
Collective fault ( TRUE = Fault )
Output
xAlarmCom
BOOL
FALSE
Collective fault - communication ( TRUE = Fault )
Output
eErrorCodeCom
ModbusErrorCode
Error code - communication ( 0 = no error )
Output
wErrorCodeDev
WORD
0
Error code - device (0 = no error)
Output
wWarningCodeDev
WORD
0
Warning code - device (0 = no warning)
Output
xBusy
BOOL
Communication indicator ( TRUE = Communication )
Input Const
rRemoteTemp2Offset
REAL
0.0
Constant measurement offset for the transmitted temperature measured value
Input Const
rRemotePressure1Offset
REAL
0.0
Constant measurement offset for the transmitted pressure - measured value
Input Const
xEnWatchdog
BOOL
FALSE
Affecting: Outputs: rRemotePressure1 Enable / disable of the communication watchdog FALSE = disabled / TRUE = enabled If the watchdog is enabled, after a period of 5s (fixed, not adjustable) during which no Modbus telegram has been received, a switch to LOCAL mode occurs When the watchdog is enabled, address 12 is therefore updated cyclically at an interval of 2.5s to reliably prevent watchdog triggering.
Input Const
eOperationMode
Grundfos_ControlStatFb
0
Pump operating mode (control / regulation) 0 = speed control
Input Const
xRemoteAccess
BOOL
TRUE
Enable / disable local operation
Input Const
tTimeUpdateSetp
TIME
TIME#45s0ms
Update interval for the operations influenced by the input ‘xUpdateSetp’
Input Const
tTimeUpdateActual
TIME
TIME#3s0ms
Update interval for the operations influenced by the input ‘xUpdateActual’
Last updated

