SimpleWriteValueFloat
SimpleWriteValueFloat (FB)
SimpleWriteValueFloat (FB)FUNCTION_BLOCK SimpleWriteValueFloat
Representation

Use of type conversion operators (e.g. INT_TO_REAL) directly at the input InputValue
InputValueIn this configuration, compiler error messages of type C0032 are generated, a download is not possible.
Remedy:
Use of an intermediate variable of the explicit type REAL directly at the output of the type conversion operator. Connecting the intermediate variable at the input InputValue.
CODESYS
InOut:
Input
xEn
BOOL
TRUE
Enable / disable communication (TRUE = enable)
Input
byUnitId
BYTE
0
Device address
Input
InputValue
__SYSTEM.AnyType
Input variable (FC16) (REAL, LREAL)
Input
rMultiplier
REAL
1.0
Multiplier for the input variable
Input
xUpdateSetp
BOOL
FALSE
Update of setpoints (on every rising edge)
Input
xResError
BOOL
FALSE
Reinitialization of the outputs eErrorCodeCom or
eErrorCodeDev to the error-free state (on every
rising edge)
Inout
ModbusClient
ModbusClientBase
Client of the device
Output
wRegisterAddrFb
WORD
Feedback - start address of the register for the Modbus- telegram
Output
eFormatFb
SIMPLE_WRITE_FORMAT_CODE
Feedback - format of the floating-point number
Output
eTypeInputValue
SIMPLE_WRITE_VALUE_TYPE_CODE
SIMPLE_WRITE_VALUE_TYPE_CODE.STATE_INVALID
State of the sign of the value at the input InputValue
Output
xAlarm
BOOL
Collective fault (TRUE = fault)
Output
xAlarmCom
BOOL
Collective fault - communication (TRUE = fault)
Output
eErrorCodeCom
ModbusErrorCode
Error code - communication (0 = no error)
Output
eErrorCodeDev
SIMPLE_WRITE_VALUE_ERROR_CODE
Error code - device (0 = no error)
Output
xBusy
BOOL
Communication indicator (TRUE = communication)
Input Const
lrDevMinus_64Bit
LREAL
0.0
Maximum negative change in value before triggering a transmission (64 bit)
Input Const
lrDevPlus_64Bit
LREAL
0.0
Maximum positive change in value before triggering a transmission (64 bit)
Input Const
rDevMinus_32Bit
REAL
0.0
Maximum negative change in value before triggering a transmission (32 bit)
Input Const
rDevPlus_32Bit
REAL
0.0
Maximum positive change in value before triggering a transmission (32 bit)
Input Const
xSwapValue
BOOL
TRUE
Enable / disable swapping the byte positions of a register (16 bit) (only relevant for 32 / 64 bit)
Input Const
xBigEndian
BOOL
TRUE
Position of the most significant 8 bits in a datum (only relevant for 32 / 64 bit)
Input Const
eFormat
SIMPLE_WRITE_FORMAT_CODE
SIMPLE_WRITE_FORMAT_CODE.IEEE754_32BIT
FALSE = most significant 8 bits are sent last // TRUE = most significant 8 bits are sent first Format of the floating-point number
Input Const
wRegisterAddr
WORD
Start address of the register for the Modbus telegram
Input Const
tTimeUpdateSetp
TIME
TIME#0ms
Update interval for the processes influenced by the input
xUpdateSetp influenced
Last updated

