BD_SENSORS_DCT_531
BD_SENSORS_DCT_531 (FB)
BD_SENSORS_DCT_531 (FB)FUNCTION_BLOCK BD_SENSORS_DCT_531
Representation

InOut:
Input
xEn
BOOL
TRUE
Enable / disable of communication ( TRUE = enabled )
Input
byUnitId
BYTE
0
Address of the device
Input
xUpdateActual
BOOL
FALSE
Update of actual values ( on every rising edge )
Input
xUpdateInfo
BOOL
FALSE
Update of device information (on every rising edge)
Inout
ModbusClient
ModbusClientBase
Client of the device
Output
rPressureUnit
REAL
Current pressure value in the unit of measurement
Output
rPressureMinUnit
REAL
Minimum value - pressure value in the unit of measurement ( measured value memory )
Output
rPressureMaxUnit
REAL
Maximum value - pressure value in the unit of measurement ( measured value memory )
Output
rPressureRangeMinUnit
REAL
Minimum value - measurement range in the unit of measurement
Output
rPressureRangeMaxUnit
REAL
Maximum value - measurement range in the unit of measurement
Output
sUnit
STRING
Unit of measurement
Output
xSensorOffsetInDevice
BOOL
Indicates whether the sensor calibration must be performed in the device ( TRUE = calibration required in device, FALSE = calibration required in FB )
Output
dwSerialNum
DWORD
Device serial number
Output
xAlarm
BOOL
FALSE
Collective fault ( TRUE = Fault )
Output
xAlarmCom
BOOL
FALSE
Collective fault - communication ( TRUE = Fault )
Output
eErrorCodeCom
ModbusErrorCode
Error code - communication ( 0 = no error )
Output
xBusy
BOOL
Communication indicator ( TRUE = Communication )
Input Const
rPressureOffset
REAL
0.0
Constant measurement offset for the transmitted pressure - measured value
Input Const
diAdrOffset
DINT
0
Offset for calculating Modbus addresses (from the Modbus registers) (Allowed range: -1, 0, +1)
Input Const
tTimeUpdateInfo
TIME
TIME#0ms
Update interval for operations affected by the input 'xUpdateInfo'
Input Const
tTimeUpdateActual
TIME
TIME#3s0ms
Update interval for the operations influenced by the input ‘xUpdateActual’
Last updated

