HVACModbus Library

Modbus function blocks RTU/TCP from various manufacturers

Placeholder: HVACModbus (Calling function blocks via **HVACModbus.**xyz)

License notice: This library requires the following licenses on the controller: - HVAC Building Automation Package SL from the CODESYS Store. For more information about licensing, please see here.

For the documentation of the HVACModbus library The library was created and tested in the specified CODESYS version. Therefore it is recommended to use this CODESYS version.

Current version

1.1.0.49 - HVACModbus CODESYS 3.5.17.2 - Download

Release Date 11.07.2025

Changes

  • FB 'BELIMO_P_22RTX_1U00X_2_FULL'

    • Operating mode - parameter 'eEcoBoostOnOffIconMode' = BELIMO_P_22RTX_1U00X_2_ICON_MODE.PRESENCE_BUTTON: The parameter 'xVisuPresence' is now declared as input 'xVisuPresence'. Each rising edge on the parameter 'xVisuPresence' generates a pulse with the time duration 'tTimeButtonPulse' at the output 'xButtonPresence'

    • Restrictions:

      • The external FB 'HVAC.Button1' must not be operated with the following parameter settings:

        • xEnClockButton = false

        • xEnToggle = false

      • The two parameters mentioned above must not be changed while online. Reason: The FB 'HVAC.Button1' does not detect parameter changes during online operation

    • An updated application representation 'BELIMO_P_22RTX_1U00X_2_FULL_ANWENDUNG' has been added.

    • Adjustment of the documentation

  • FB 'SPLUSS_RYMASKON_2XX_MOD_V2'

    • Bug fix in the area of offset determination:

      • rRoomTempOffset

      • rRelHumidityOffset

      • rExtTempOffset

  • FB 'SPLUSS_RYMASKON_2XX_MOD'

    • Bug fix in the area of offset determination:

      • rRoomTempOffset

      • rRelHumidityOffset

      • rExtTempOffset


Older versions

1.1.0.48 - HVACModbus CODESYS 3.5.17.2 - Download

Release Date 30.05.2025

Changes

  • FB 'SAMSUNG_INTESIS_IDU_FC04_RXXX0_RXX38'

    • Reduction from 3 communication operations to one communication operation (FC03: XXX0 - XX38) after testing on a real gateway

  • FB 'BELIMO_P_22RTX_1U00X_2_FULL'

    • Operating mode - parameter 'eEcoBoostOnOffIconMode' = BELIMO_P_22RTX_1U00X_2_ICON_MODE.PRESENCE_BUTTON: Each rising edge on the parameter 'xVisuPresence' generates a pulse with the time duration 'tTimeButtonPulse' at the output 'xButtonPresence'. Restrictions:

      • The external FB 'HVAC.Button1' must not be operated with the following parameter settings:

        • xEnClockButton = FALSE

        • xEnToggle = FALSE

      • The two parameters mentioned above must not be changed during online operation (Reason: The FB 'HVAC.Button1' does not detect parameter changes during online operation)

    • Adjustment of the documentation

1.1.0.47 - HVACModbus CODESYS 3.5.17.2 - Download

Release Date 05/06/2025

New features

  • FB 'SAMSUNG_INTESIS_IDU_FC04_RXXX0_RXX38'

Changes

  • Parameter changes of the function blocks of all devices with writable setpoints (initial value). This is intended to ensure that setpoints are transmitted reliably in a timely manner.

    • old: 'tTimeUpdateSetp' = T#0s

    • new: 'tTimeUpdateSetp' = T#45s

  • FB 'BELIMO_CQ24A_BAC_MOD'

    • Parameter 'eRelPosMode' added

      • BELIMO_CQ24A_BAC_MOD_RELPOS_MODE.RELATIVE_TO_RMAX: rRelPos: Calculated value relative to parameter 'rMax' in %. Example: rMax = 60.0 %, direct value from device = 50 %, rRelPos = 83.33 %

      • BELIMO_CQ24A_BAC_MOD_RELPOS_MODE.DEVICE_VALUE: rRelPos: Direct value from the device in %

  • FB 'ResolveAddressAsync'

    • new attribute 'hide' added

  • FB 'TwoPoint'

    • new attribute 'hide' added

  • All function blocks: The permissible range for Modbus device addresses is uniformly set to 1..255 (RTU and TCP).

  • FB 'BELIMO_P_22RTX_1U00X_2_FULL': Operating mode 'PRESENCE_BUTTON' - The parameter 'xEcoIconPresenceButtonMode' defines the function/display of the ECO icon on the RBG:

    • FALSE: no display / function present

    • TRUE: display and function present, the operating mode switches with each press of the ECO icon from 'ON_COMFORT' to 'ECO_MODE' and back.

  • FB 'ModbusClient_TCP': Behavior optimized in the error case 'Number of received user data <> Number of requested user data'.

  • FB 'ModbusClient_TCP_Fast': optimized in the error case 'Number of received user data <> Number of requested user data'.

1.1.0.46 - HVACModbus CODESYS 3.5.17.2 - Download

Release Date 28.11.2024

New features

  • FB 'FINDER_7M_24_8_230_0212'

  • FB 'SPLUSS_714X_MOD'

  • FB 'SPLUSS_724X_MOD'

  • FB 'SPLUSS_LCD_SHD_MODBUS_EASY'

  • FB 'BELIMO_EPXXXR2_BAC_FW_4_2_0_MOD'

Changes

  • FB 'LOYTEC_LSTAT_80X_GX_LX_MOD'

    • Error in detection of the product code fixed

  • FB 'ABB_B21_23_24'

    • Detection of device subversion added (Steel, Bronze, Silver)

    • Detection of device version added (B21, B23, B24)

    • Definition of maximum values to represent actually existing measured variables

    • Function: If an actual value of a measured variable exceeds its assigned maximum value, '0.0' is displayed at the measured variable's output

  • Adjustment of the Modbus telegrams (Unused registers must not be read)

    • FB 'OPPERMANN_P_MOD_W16'

    • FB 'OPPERMANN_HT_MOD_I_XXX'

    • FB 'OPPERMANN_PV_MOD_ADX'

    • FB 'OPPERMANN_T_MOD_I_XXX'

  • FB 'BELIMO_P_22RTX_1U00X_2_FULL'

    • Bug fix - output 'rOffset'

  • FB 'BELIMO_P_22RTX_1U00X_2_EASY'

    • FB removed without replacement

1.1.0.44 - HVACModbus CODESYS 3.5.17.2 - Download

Release Date 28.11.2024

New features

  • FB 'OPPERMANN_HT_MOD_I_XXX'

  • FB 'OPPERMANN_KRM_X_2_MOD'

  • FB 'OPPERMANN_MSX_MOD_I_80_XX_X_XXX'

  • FB 'OPPERMANN_PV_MOD_ADX'

  • FB 'OPPERMANN_P_MOD_W16'

  • FB 'OPPERMANN_T_MOD_I_XXX'

  • FB 'KAMSTRUP_MULTICAL_XX3_DEFAULT'

  • FB 'THERMOKON_WRF07_TEMP_HUMIDITY'

  • FB 'THERMOKON_WRF07_TEMP_HUM_AO2V_REV_A_H'

  • FB 'BELIMO_EPXXXX_FW_3_0_8_MOD

    • This function block is suitable for all 'EP' valves with firmware 3_0_8 (status 09/2024).

  • FB DAIKIN_EKMBDXB7V1_IDU_FC16_2000_2143

    • In this function block only the setpoints of indoor units 1-0 to 3-15 are updated.

Changes

  • FB 'OPPERMANN_KRM_2_DZ_MOD' and 'OPPERMANN_KRM_X_2_MOD':

    • Output 'xSmokeAlarm'

      • Function previously: active if output 'wSensor' ≥ 255

      • Function now: active if output 'eState' = 'DEVICE_FAULT' or 'DEVICE_ALARM' or 'DEVICE_FAULT_ALARM'

  • FB 'LOYTEC_LSTAT_80X_GX_LX_MOD'

    • Automatic detection of the product code added

    • CO2 sensor and presence detection added

    • Input 'xResToSetpTempBase' added (on each rising edge the setpoint temperature offset is set to 0.0)

  • All FBs: Function of the output 'xAlarmCom'

    • The output becomes active if, continuously for a centrally adjustable time period (global constant 'gc_Parameters.gc_tOnDelayxAlarmCom'), at least one of the following conditions is present:

      • The connection between the associated client (output 'xConnected' = false) and the connected server is interrupted.

      • A communication error is detected after the completion of each communication (request and response telegram).

    • The output becomes inactive if none of the conditions described above are present anymore.

  • All FBs: Function of the output 'eErrorCodeCom'

    • The output 'eErrorCodeCom' always holds the last active communication error. It can be reset by a rising edge at the input 'xResError'.

  • FB 'BELIMO_EVXXXF_FW_3XX_MOD'

    • Error at output 'eAO' fixed

    • Error at output 'st'ErrorCodeDev' fixed

  • FB 'SPLUSS_TM65_MOD_V2' moved to folder 'Reserve'.

  • FB 'SPLUSS_TM65_MOD_V3' moved to folder 'Reserve'.

1.1.0.39 - HVACModbus CODESYS 3.5.17.2 - Download

Release Date 16.09.2024

New features

  • FB 'DAIKIN_EKMBDXB7V1_IDU_FC04_1000_1191'. This allows part of the indoor unit configuration to be read.

  • FB 'BELIMO_EVXXX_RX_FW_4_2_0_MOD'

  • FB 'BELIMO_EVXXX_RX_FW_4_0_UND_4_1_MOD'

  • FB 'BELIMO_EVXXX_F_FW_3XX_MOD'

Changes

  • FB 'THERMOKON_WRF06':

    • Changes in the area of fan stage settings.

  • FB 'THIES_WSC11_MOD'

    • Output 'rYYYMMDD' changed from data type REAL to DWORD. Rounding errors during conversion are avoided.

  • FB 'ABB_B21_23_24'

    • Counter values were changed from data type REAL to ULINT. Rounding errors during conversion are avoided.

  • FB 'FINDER_7E_46_8_400_0212'

    • Counter values were changed from data type REAL to DWORD. Rounding errors during conversion are avoided.

  • FB 'GRUNDFOS_MAGNA_3_MONO'

    • Counter values were changed from data type WORD to DWORD. Reason: Avoidance of overflow errors.

    • The following outputs were added:

      • rDiffTemp

      • dwCoolEnergyTotal

      • dwCoolVolumeTotal

  • FB 'BELIMO_P_22RTX_1U00X_2_FULL'

    • Bug in calculation of the room setpoint temperature due to switching of operating modes fixed.

    • Operating mode: 'OPERATION_MODE': Bug in calculation of the room setpoint temperature when operated at the RBG fixed.

  • FB 'BELIMO_P_22RTX_1U00X_2_EASY'

    • Output 'eEcoBoostOnOffIconMode' added to display the current operating mode.

    • Bug in calculation of the room setpoint temperature due to switching of operating modes fixed.

    • Operating mode 'OPERATION_MODE: Bug in calculation of the room setpoint temperature when operated at the RBG fixed.

1.1.0.38 - HVACModbus CODESYS 3.5.17.2 - Download

Release Date 17.06.2024

New features

  • new FB 'DAIKIN_EKMBDXB'. Function block for the Modbus interface for up to 64 indoor units.

Changes

  • FB 'THERMOKON_WRF06':

    • Bug in the area of analog outputs AO01 and AO02 fixed

    • Bug in the area of fan stage settings fixed

  • FB 'SPLUSS_2328_MOD_LCD'

    • Error in the output of the pressure actual values corrected

1.1.0.37 - HVACModbus CODESYS 3.5.17.2 - Download

Release Date 16.05.2024

New features

  • new FB 'BELIMO_P_22RTX_1U00X_2_FULL'. This FB allows the complete configuration (addresses 110..149) of all parameters in the 'Service' area. Use of the 'Belimo Assistant' app is therefore optional.

  • new FB 'BELIMO_P_22RTX_1U00X_2_EASY'. This FB reads the complete configuration (addresses 110..149) of all parameters in the 'Service' area (once at startup, on each rising edge at input 'xUpdateConfig' or cyclically at interval 'tTimeUpdateConfig'). The parameters are set in the 'Belimo Assistant' app. The following parameters cannot be set in the app:

    • eTemperatureUnit (address 120)

    • eOffsetUnit (address 122)

    • eDsplIconsHeatCool (address 134)

    • eWarningIconFunct (address 135)

    • eWindowIconFunct (address 136)

    • Mode On/Off Button (address 141)

  • new FB 'GÜNTER_GMMNEXT'

  • new FB 'THERMOKON_WRF06'

Changes

  • FB 'DANFOSS_NOVOCON': outputs 'rAI1' and 'rAI2' added

  • all FBs with output 'xAlarmCom': The non-existing connection between Modbus-TCP client (FB 'ModbusClient_TCP' or 'ModbusClient_TCP_Fast', output 'xConnected') and Modbus-TCP server is only passed to the output 'xAlarmCom' after a time period of 'gc_tOnDelayxAlarmCom'. Previously the transfer occurred immediately.

  • FB 'EBM_SERIEN_84_112_150_200_V6_0' and 'EBM_SERIEN_84_112_150_200_V6_3':

    • Register D103: The default value was changed from 1 to 0

    • The instance 'Sollwerte_2' is transferred to the new instance 'Konfiguration_5' (because the register addresses are in the EEPROM area and must not be written cyclically)

  • FB 'EBM_SERIEN_84_112_150_200_V5_0'

    • The instance 'Sollwerte_1' is transferred to the new instance 'Konfiguration_2' (because the register addresses are in the EEPROM area and must not be written cyclically)

    • The instance 'Sollwerte_2' is transferred to the new instance 'Konfiguration_3' (because the register addresses are in the EEPROM area and must not be written cyclically)

    • The instance 'Sollwerte_3' is transferred to the new instance 'Konfiguration_4' (because the register addresses are in the EEPROM area and must not be written cyclically)

1.1.0.36 - HVACModbus CODESYS 3.5.17.2 - Download

Release Date 15.01.2024

New features

  • new FB 'THERMOKON_WRF07_CO2_VOC'

1.1.0.35 - HVACModbus CODESYS 3.5.17.2 - Download

Release Date 04.01.2024

New features

  • Introduction of parameters for measured value adjustment (=offset)

    • GRUNDFOS_MAGNA_3_MONO

    • IMI_TA_SLIDER_160

    • KAMPMANN_FAN_COIL

    • POWERIO_T1_R100

    • POWERIO_T1_R100_V2

    • POWERIO_T1_R300

    • POWERIO_T1_R310

    • PRIGNITZ_CIT2

    • ROSENBERG_FAN_EC_MOTOR

    • THERMOKON_NOVOS_TOUCH

    • THERMOKON_NOVOS_TOUCH_V2

    • THERMOKON_WRF07

    • THIES_WSC11_MOD

    • TROX_BM0

    • TROX_VRU_BUDN

    • TROX_XM0

    • AERASGARD SPLUSS_FSFTM_CO2_MOD

    • AERASGARD SPLUSS_FSFTM_CO2_POTI_MOD (new function block)

    • HYGRASGARD SPLUSS_FSFTM_MOD

    • HYGRASGARD SPLUSS_FSFTM_POTI_MOD (new function block)

    • AERASGARD SPLUSS_KFTM_LQ_CO2_MOD

    • AERASGARD SPLUSS_AFTM_LQ_CO2_MOD (new function block)

    • AERASGARD SPLUSS_RFTM_XXX_MOD (new function block)

    • AERASGARD SPLUSS_RFTM_CO2_POTI_MOD (new function block)

    • AERASGARD SPLUSS_RFTM_LQ_PS_CO2_WITHOUT_POT_REV2022_MOD

    • HYGRASGARD SPLUSS_AFTF_MOD

    • HYGRASGARD SPLUSS_KFTF_MOD

    • HYGRASGARD SPLUSS_RPFTF_MOD

    • HYGRASGARD SPLUSS_TW_MOD

    • HYGRASGARD SPLUSS_VFTF_MOD

    • PREMASGARD SPLUSS_2327_MOD_LCD

    • PREMASGARD SPLUSS_2328_MOD_LCD

    • PREMASGARD SPLUSS_8147_MOD_LCD

    • PREMASGARD SPLUSS_8148_MOD_LCD

    • THERMASGARD SPLUSS_ALTM1_MOD

    • THERMASGARD SPLUSS_ALTM2_MOD

    • THERMASGARD SPLUSS_ATM2_MOD

    • THERMASGARD SPLUSS_HFTM_MOD

    • THERMASGARD SPLUSS_MWTM_MOD

    • THERMASGARD SPLUSS_RPTM1_MOD

    • THERMASGARD SPLUSS_RPTM2_MOD

    • THERMASGARD SPLUSS_TM65_MOD

    • THERMASGARD SPLUSS_TM65_MOD_V2

    • THERMASGARD SPLUSS_TM65_MOD_V3

    • THERMASGARD SPLUSS_RTM1_MOD

    • SPLUSS_RYMASKON_2XX_MOD

    • SPLUSS_RYMASKON_2XX_MOD_V2

    • SPLUSS_RYMASKON_5XX_MOD

    • SPLUSS_RYMASKON_7XX_MOD

1.1.0.34 - HVACModbus CODESYS 3.5.17.2 - Download

Release Date 11.12.2023

New features

  • Introduction of parameters for measured value adjustment (=offset)

    • BD_SENSORS_DCT_531

    • BELIMO_GR24A_MOD_5

    • BELIMO_LM24A_MOD

    • BELIMO_LR24A_MOD

    • BELIMO_LR24A_MOD_V2

    • BELIMO_NM24A_MOD

    • BELIMO_NR24A_MOD

    • BELIMO_NV24A_MOD

    • BELIMO_PRCA_BAC_S2_T

    • BELIMO_SF24A_MOD

    • BELIMO_VRU_D3_BAC_FULL

    • BELIMO_VSR24A_LP1_MOD

    • ELSNER_P03_3_MODBUS_MIT_GPS

Changes

  • FB

1.1.0.32 - HVACModbus CODESYS 3.5.17.2 - Download

Release Date 30.11.2023

New features and changes

  • FB 'SimpleWriteCoil_FC05'. This FB allows writing 1 Coil (FC05)

  • FB 'SimpleWriteCoils_FC15'. This FB allows writing 2 to 64 Coils (FC15). With the FB 'SimpleWriteValueCoil', however, only 8, 16, 32 or 64 Coils can always be written simultaneously with FC15.

Changes

  • FB 'SPLUSS_RYMASKON_7XX_MOD': Elimination of errors related to capturing the current room setpoint temperature in the day operation of the RBG.

  • FB 'SPLUSS_RYMASKON_5XX_MOD': Elimination of errors related to capturing the current room setpoint temperature in the day operation of the RBG.

1.1.0.31 - HVACModbus CODESYS 3.5.17.2 - Download

Release Date 30.10.2023

Changes

FB 'DANFOSS_NOVOCON'

When writing the valve type (eValveType), some internal registers of the valve actuator are initialized. By changing the FB, all relevant configuration parameters and outputs are now retransmitted to the valve actuator when the valve type is changed.

1.1.0.30 - HVACModbus CODESYS 3.5.17.2 - Download

Release Date 26.09.2023

Fixing errors from version 1.1.0.29 related to the FB 'SimpleReadCoilInput'. Affected methods:

  • SendReadRequest

  • OnResponseComplete

1.1.0.29 - HVACModbus CODESYS 3.5.17.2 - Download

Release Date 21.09.2023

New features and changes

  • new FB 'BELIMO_C615QP_B_MOD'

  • FB 'SIEMENS_PAC_3200' adapted

  • new FB 'SimpleReadCoilInput'

    • This new function block allows reading 1 - 64 Coils or Inputs (FC01 / FC02)

    • With the FB 'SimpleReadValue', however, only 16, 32 or 64 Coils or Inputs can always be read simultaneously

1.1.0.28 - HVACModbus CODESYS 3.5.17.2 - Download

Release Date 24.08.2023

New features and changes

  • new FB 'ModbusClient_TCP_Fast'

    • This FB corresponds to the previous FB 'ModbusClient_TCP'. Two states of the state machine were removed to increase the transmission rate of Modbus telegrams in the client-server connection.

  • FB 'DANFOSS_NOVOCON' adapted

  • FB 'KAMPMANN_FAN_COIL' changed

    • Registers 198...201 must not be written in one telegram because register 200 is not defined.

    • Registers 210...215 must not be written in one telegram because registers 212..214 are not defined.

1.1.0.27 - HVACModbus CODESYS 3.5.17.2 - Download

Release Date 04.08.2023

New features and changes

  • new FB 'BELIMO_VSR24A_LP1_MOD'

1.1.0.26 - HVACModbus CODESYS 3.5.17.2 - Download

Release Date 17.07.2023

New features

  • new FB 'SimpleWriteArrayOfWord'

  • new FB 'SimpleWriteArrayOfInt'

1.1.0.25 - HVACModbus CODESYS 3.5.17.2 - Download

Release Date 07.07.2023

New features and changes

  • new FB 'SimpleReadArray'

  • FB 'KAMPMANN_FAN_COIL'

    • Bug in transmission of the virtual room temperature (register 75) fixed

  • All FBs: Check of pointers for validity

1.1.0.24 - HVACModbus CODESYS 3.5.17.2 - Download

Release Date 28.06.2023

New features and changes

  • FB 'HELIOS_KWL_MODBUS_GATEWAY'

    • Renaming:

      • 'rSetpFanStage' setpoint fan stage

      • 'rSetpFanStage_Fb' active fan stage

    • Extension:

      • 'rSetpTemp' setpoint comfort temperature

      • 'rSetpTemp_Fb' feedback setpoint comfort temperature

      • 'xUpdateSetp' update of setpoints

      • 'tTimeUpdateSetp' update interval

      • 'rSetpFanStageMin' active minimum fan stage

  • new FB 'BELIMO_VRU_D3_BAC_EASY'

  • new FB 'BELIMO_VRU_D3_BAC_FULL'

  • All FBs in folder 'Manufacturer Modbus Devices'

    • The output 'xAlarmCom' becomes active (=TRUE) without time delay if the output 'xConnected' of the corresponding FB 'ModbusClient_TCP' becomes inactive (=FALSE)

  • Update of the library 'SysSocket' to 3.5.18.40

  • Update of the library 'SysSocket2' to 3.5.18.40

1.1.0.23 - HVACModbus CODESYS 3.5.17.2 - Download

Release Date 16.06.2023

Complete overhaul, bug fixes, functional improvements and migration of the TCP library to the SysSocket2 library.

New features and changes

  • FB 'ModbusClient_TCP'

    • The state machine now has more states than before (advantages for troubleshooting, disadvantageous with large task cycle times)

    • The method 'ReadyForReceive' reliably and quickly detects a broken client-server connection

    • Input 'xEn' added

    • Output 'xReady' added

    • Changes to the parameters 'sHostAddress' or 'wPort' are detected and cause the teardown of the previous and the establishment of the new connection

    • Number of timeout parameters reduced to 4

    • Known deficiency: In the 'Ready' state a broken client-server connection is still not detected!

1.1.0.22 - HVACModbus CODESYS 3.5.17.2 - Download

Release Date 18.04.2023

New features and changes

  • FB 'ModbusClient_TCP'

    • Parameter 'xCheckServer': Initial value = TRUE (cyclic checking of the client-server connection is active)

    • Parameter 'tTimeCheckServer': Initial value = 60s (cyclic check of the client-server connection every 60s, if xCheckServer = TRUE).

    • Parameter 'tTimeoutServerConnect' renamed to 'tTimeoutServerConnectMin'

    • Parameter 'tTimeoutServerConnectMax' (initial value = 24h) added.

    • After each timeout in the 'CONNECT' state the duration of the next timeout is doubled (maximum value: tTimeoutServerConnectMax)

    • Changes to the input 'sHostAddress' are detected and cause the reestablishment of the connection.

    • Changes to the input 'wPort' are detected and cause the reestablishment of the connection.

  • FB 'SIEMENS_PAC_3200'

    • Output 'rOperatingHours' (operating hours) added.

1.1.0.21 - HVACModbus CODESYS 3.5.17.2 - Download

Release Date 18.04.2023

New features and changes

  • FB 'ModbusClient_TCP'

    • Parameter 'xCheckServer': Initial value = TRUE (cyclic checking of the client-server connection is active)

    • Parameter 'tTimeCheckServer': Initial value = 60s (cyclic check of the client-server connection every 60s, if xCheckServer = TRUE).

    • Parameter 'tTimeoutServerConnect' renamed to 'tTimeoutServerConnectMin'

    • Parameter 'tTimeoutServerConnectMax' (initial value = 24h) added.

    • After each timeout in the 'CONNECT' state the duration of the next timeout is doubled (maximum value: tTimeoutServerConnectMax)

    • Changes to the input 'sHostAddress' are detected and cause the reestablishment of the connection.

    • Changes to the input 'wPort' are detected and cause the reestablishment of the connection.

  • FB 'SIEMENS_PAC_3200'

    • Output 'rOperatingHours' (operating hours) added.

1.1.0.20 - HVACModbus CODESYS 3.5.17.2 - Download

Release Date 12.08.2022

New features and changes

  • n.a.

1.0.0.3 - HVACModbus CODESYS 3.5.14.0 - Download

Release Date 12.08.2020

New features and changes

  • n.a.

Last updated