# POWERIO\_T1\_BSK1\_XXX\_ECO\_FULL

## `POWERIO_T1_BSK1_XXX_ECO_FULL` (FB)

`FUNCTION_BLOCK` POWERIO\_T1\_BSK1\_XXX\_ECO\_FULL

### Darstellung

<figure><img src="/files/Ps8lGmIJ7Fw1mS71nNGk" alt=""><figcaption></figcaption></figure>

InOut:

| Scope       | Name                 | Type                             | Initial      | Comment                                                                                                                                                                                         |
| ----------- | -------------------- | -------------------------------- | ------------ | ----------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------- |
| Input       | `xEn`                | `BOOL`                           | TRUE         | Freigabe / Sperrung der Kommunikation (TRUE = Freigabe)                                                                                                                                         |
| Input       | `byUnitId`           | `BYTE`                           | 0            | Adresse des Geräts                                                                                                                                                                              |
| Input       | `xUpdateActual`      | `BOOL`                           | FALSE        | <p>Aktualisierung der Istwerte (bei jeder ansteigenden Flanke<br>)</p>                                                                                                                          |
| Input       | `xUpdateSetp`        | `BOOL`                           | FALSE        | <p>Aktualisierung der Sollwerte (bei jeder ansteigenden Flanke<br>)</p>                                                                                                                         |
| Input       | `xResError`          | `BOOL`                           | FALSE        | <p>Reinitialisierung des Ausgangs <code>eErrorCodeCom</code> in den<br>fehlerfreien Zustand / Rücksetzung des Fehlerstatuses der<br>Brandschutzklappen (bei jeder ansteigenden Flanke)</p>      |
| Input       | `xFD1`               | `BOOL`                           | FALSE        | <p>Festlegung des Zustands des Ausgangs der Brandschutzklappe 1<br>(FALSE = Geschlossen)</p>                                                                                                    |
| Input       | `xResAutoFDx`        | `BOOL`                           | FALSE        | <p>Umschaltung der Handübersteuerung der Ausgänge für die<br>Brandschutzklappen in den Automatikbetrieb (bei jeder<br>ansteigenden Flanke)</p>                                                  |
| Input       | `xSendSysCommand`    | `BOOL`                           | FALSE        | <p>Aktivierung der Übertragung des Systembefehls (Register 6)<br>(bei jeder ansteigenden Flanke UND wSysCommand > 0)</p>                                                                        |
| Inout       | `ModbusClient`       | `ModbusClientBase`               |              | Client des Geräts                                                                                                                                                                               |
| Output      | `xFD1_Open`          | `BOOL`                           |              | Rückmeldung - Brandschutzklappe 1 geöffnet (TRUE = Offen)                                                                                                                                       |
| Output      | `xFD1_Closed`        | `BOOL`                           |              | <p>Rückmeldung - Brandschutzklappe 1 geschlossen (TRUE =<br>Geschlossen)</p>                                                                                                                    |
| Output      | `xFD1_Fb`            | `BOOL`                           |              | <p>Rückmeldung - Zustand des Ausgangs der Brandschutzklappe 1 (<br>FALSE = Geschlossen)</p>                                                                                                     |
| Output      | `eAOO_FD1`           | eManBin                          |              | <p>Zustand der Handübersteuerung am Ausgang der<br>Brandschutzklappe 1</p>                                                                                                                      |
| Output      | `tRT_FD1_Closed`     | `TIME`                           |              | <p>Laufzeit des letzten Schliessvorgangs der BSK 1 (<br>Bedingungen: xFD1 = von TRUE nach FALSE bis xFD1Closed =<br>TRUE)</p>                                                                   |
| Output      | `tRT_FD1_Open`       | `TIME`                           |              | <p>Laufzeit des letzten Öffnungsvorgangs der BSK 1 (<br>Bedingungen: xFD1 = von FALSE nach TRUE bis xFD1Open = TRUE<br>)</p>                                                                    |
| Output      | `tDT_FD1_Closed`     | `TIME`                           |              | <p>Totzeit des letzten Schliessvorgangs der BSK 1 (<br>Bedingungen: xFD1 = von TRUE nach FALSE bis xFD1Open = von<br>TRUE nach FALSE)</p>                                                       |
| Output      | `tDT_FD1_Open`       | `TIME`                           |              | <p>Totzeit des letzten Öffnungsvorgangs der BSK 1 (<br>Bedingungen: xFD1 = von FALSE nach TRUE bis xFD1Closed = von<br>TRUE nach FALSE)</p>                                                     |
| Output      | `eTypeID`            | POWERIO\_T1\_BSK1\_XXX\_ID\_TYPE |              | Identifikation des Geräts                                                                                                                                                                       |
| Output      | `wFirmwareVer`       | `WORD`                           |              | Firmware-Version des Geräts                                                                                                                                                                     |
| Output      | `xAlarm`             | `BOOL`                           | FALSE        | Sammelstörung (TRUE = Störung)                                                                                                                                                                  |
| Output      | `xAlarmCom`          | `BOOL`                           | FALSE        | Sammelstörung - Kommunikation (TRUE = Störung)                                                                                                                                                  |
| Output      | `eErrorCodeCom`      | ModbusErrorCode                  |              | Fehlercode - Kommunikation (0 = kein Fehler)                                                                                                                                                    |
| Output      | `stErrorCodeFD1`     | `STRING`                         |              | <p>String mit den Bit-Nummern der aktiven Fehler der<br>Brandschutzklappe 1 (‘’ = kein Fehler)</p>                                                                                              |
| Output      | `xBusy`              | `BOOL`                           |              | Kommunikationsanzeige (TRUE = Kommunikation)                                                                                                                                                    |
| Input Const | `xEnMonitoring`      | `BOOL`                           | TRUE         | <p>Festlegung der Aktivierung / Deaktivierung der Zeitmessungen<br>/ der BSK-Überwachung (TRUE = Ein)</p>                                                                                       |
| Input Const | `xDIxInversion`      | `BOOL`                           | FALSE        | <p>Festlegung der Invertierung der Digitaleingänge DIx (FALSE:<br>keine Invertierung // TRUE = Invertierung)</p>                                                                                |
| Input Const | `wSysCommand`        | `WORD`                           | 0            | <p>Wert des zu übertragenden System-Befehls (FC06 - Register 6<br>) (0 = keine Funktion, Werte > 0 siehe Dokumentation<br>T1\_BSK1\_XXX)</p>                                                    |
| Input Const | `wFD1PrescTime`      | `WORD`                           | 10           | <p>Vorteiler für alle Zeiten der Brandschutzklappe 1 (lesend /<br>schreibend) (interne Zeitbasis = 0.1s)</p>                                                                                    |
| Input Const | `xFD1_SafeState_Sta` | `BOOL`                           | TRUE         | <p>Zustand des Digitalausgang für die Brandschutzklappe 1 im<br>Safestate-Betrieb (TRUE = Geöffnet)</p>                                                                                         |
| Input Const | `xFD1_SafeState_En`  | `BOOL`                           | FALSE        | <p>Freigabe / Sperrung des Digitalausgangs für die<br>Brandschutzklappe 1 für den Safestate-Betrieb (TRUE =<br>Freigabe)</p>                                                                    |
| Input Const | `tDT_FD1Open`        | `TIME`                           | TIME#10s0ms  | <p>Maximale Zeitdauer der Totzeit bei der Öffnung der<br>Brandschutzklappe 1</p>                                                                                                                |
| Input Const | `tDT_FD1Closed`      | `TIME`                           | TIME#10s0ms  | <p>Maximale Zeitdauer der Totzeit bei der Schliessung der<br>Brandschutzklappe 1</p>                                                                                                            |
| Input Const | `tRT_FD1Open`        | `TIME`                           | TIME#3m0s0ms | <p>Maximale Zeitdauer der vollständigen Öffnung der<br>Brandschutzklappe 1</p>                                                                                                                  |
| Input Const | `tRT_FD1Closed`      | `TIME`                           | TIME#3m0s0ms | <p>Maximale Zeitdauer der vollständigen Schliessung der<br>Brandschutzklappe 1</p>                                                                                                              |
| Input Const | `tTimeSafeState`     | `TIME`                           | TIME#0ms     | <p>Zeitdauer für die Aktivierung des Zustands <code>Safestate</code> bei<br>Kommunikationsausfall (0 = keine Timeout-/Safe-State-<br>Funktion, ganzzahlige Vielfache von 1s, mindestens 5s)</p> |
| Input Const | `tTimeUpdateSetp`    | `TIME`                           | TIME#0ms     | <p>Updateintervall für die Vorgänge, die durch den Eingang<br><code>xUpdateSetp</code> beeinflusst werden</p>                                                                                   |
| Input Const | `tTimeUpdateActual`  | `TIME`                           | TIME#500ms   | <p>Updateintervall für die Vorgänge, die durch den Eingang<br><code>xUpdateActual</code> beeinflusst werden</p>                                                                                 |


---

# Agent Instructions: Querying This Documentation

If you need additional information that is not directly available in this page, you can query the documentation dynamically by asking a question.

Perform an HTTP GET request on the current page URL with the `ask` query parameter:

```
GET https://support.powerio.com/hub/codesys-hvac/hvac-modbus-library/functionblocks/powerio/powerio_t1_bsk1_xxx_eco_full.md?ask=<question>
```

The question should be specific, self-contained, and written in natural language.
The response will contain a direct answer to the question and relevant excerpts and sources from the documentation.

Use this mechanism when the answer is not explicitly present in the current page, you need clarification or additional context, or you want to retrieve related documentation sections.