> For the complete documentation index, see [llms.txt](https://support.powerio.com/hub/llms.txt). Markdown versions of documentation pages are available by appending `.md` to page URLs; this page is available as [Markdown](https://support.powerio.com/hub/codesys-hvac/hvac-modbus-library/functionblocks/powerio/powerio_t1_bsk1_xxx_eco_easy.md).

# POWERIO\_T1\_BSK1\_XXX\_ECO\_EASY

## `POWERIO_T1_BSK1_XXX_ECO_EASY` (FB)

`FUNCTION_BLOCK` POWERIO\_T1\_BSK1\_XXX\_ECO\_EASY

### Darstellung

<figure><img src="/files/3niOD4eIH0rcmDvQ0VKX" alt=""><figcaption></figcaption></figure>

InOut:

| Scope       | Name                 | Type               | Initial    | Comment                                                                                                                                                                                         |
| ----------- | -------------------- | ------------------ | ---------- | ----------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------- |
| Input       | `xEn`                | `BOOL`             | TRUE       | Freigabe / Sperrung der Kommunikation (TRUE = Freigabe)                                                                                                                                         |
| Input       | `byUnitId`           | `BYTE`             | 0          | Adresse des Geräts                                                                                                                                                                              |
| Input       | `xUpdateActual`      | `BOOL`             | FALSE      | <p>Aktualisierung der Istwerte (bei jeder ansteigenden Flanke<br>)</p>                                                                                                                          |
| Input       | `xUpdateSetp`        | `BOOL`             | FALSE      | <p>Aktualisierung der Sollwerte (bei jeder ansteigenden Flanke<br>)</p>                                                                                                                         |
| Input       | `xResError`          | `BOOL`             | FALSE      | <p>Reinitialisierung des Ausgangs <code>eErrorCodeCom</code> in den<br>fehlerfreien Zustand / Rücksetzung des Fehlerstatuses der<br>Brandschutzklappen (bei jeder ansteigenden Flanke)</p>      |
| Input       | `xFD1`               | `BOOL`             | FALSE      | <p>Festlegung des Zustands des Ausgangs der Brandschutzklappe 1<br>(FALSE = Geschlossen)</p>                                                                                                    |
| Input       | `xResAutoFDx`        | `BOOL`             | FALSE      | <p>Umschaltung der Handübersteuerung der Ausgänge für die<br>Brandschutzklappen in den Automatikbetrieb (bei jeder<br>ansteigenden Flanke)</p>                                                  |
| Input       | `xSendSysCommand`    | `BOOL`             | FALSE      | <p>Aktivierung der Übertragung des Systembefehls (Register 6)<br>(bei jeder ansteigenden Flanke UND wSysCommand > 0)</p>                                                                        |
| Inout       | `ModbusClient`       | `ModbusClientBase` |            | Client des Geräts                                                                                                                                                                               |
| Output      | `xFD1_Open`          | `BOOL`             |            | Rückmeldung - Brandschutzklappe 1 geöffnet (TRUE = Offen)                                                                                                                                       |
| Output      | `xFD1_Closed`        | `BOOL`             |            | <p>Rückmeldung - Brandschutzklappe 1 geschlossen (TRUE =<br>Geschlossen)</p>                                                                                                                    |
| Output      | `xFD1_Fb`            | `BOOL`             |            | <p>Rückmeldung - Zustand des Ausgangs der Brandschutzklappe 1 (<br>FALSE = Geschlossen)</p>                                                                                                     |
| Output      | `eAOO_FD1`           | eManBin            |            | <p>Zustand der Handübersteuerung am Ausgang der<br>Brandschutzklappe 1</p>                                                                                                                      |
| Output      | `xAlarm`             | `BOOL`             | FALSE      | Sammelstörung (TRUE = Störung)                                                                                                                                                                  |
| Output      | `xAlarmCom`          | `BOOL`             | FALSE      | Sammelstörung - Kommunikation (TRUE = Störung)                                                                                                                                                  |
| Output      | `eErrorCodeCom`      | ModbusErrorCode    |            | Fehlercode - Kommunikation (0 = kein Fehler)                                                                                                                                                    |
| Output      | `stErrorCodeFD1`     | `STRING`           |            | <p>String mit den Bit-Nummern der aktiven Fehler der<br>Brandschutzklappe 1 (‘’ = kein Fehler)</p>                                                                                              |
| Output      | `xBusy`              | `BOOL`             |            | Kommunikationsanzeige (TRUE = Kommunikation)                                                                                                                                                    |
| Input Const | `xDIxInversion`      | `BOOL`             | FALSE      | <p>Festlegung der Invertierung der Digitaleingänge DIx (FALSE:<br>keine Invertierung // TRUE = Invertierung)</p>                                                                                |
| Input Const | `wSysCommand`        | `WORD`             | 0          | <p>Wert des zu übertragenden System-Befehls (FC06 - Register 6<br>) (0 = keine Funktion, Werte > 0 siehe Dokumentation<br>T1\_BSK1\_XXX)</p>                                                    |
| Input Const | `xFD1_SafeState_Sta` | `BOOL`             | TRUE       | <p>Zustand des Digitalausgang für die Brandschutzklappe 1 im<br>Safestate-Betrieb (TRUE = Geöffnet)</p>                                                                                         |
| Input Const | `xFD1_SafeState_En`  | `BOOL`             | FALSE      | <p>Freigabe / Sperrung des Digitalausgangs für die<br>Brandschutzklappe 1 für den Safestate-Betrieb (TRUE =<br>Freigabe)</p>                                                                    |
| Input Const | `tTimeSafeState`     | `TIME`             | TIME#0ms   | <p>Zeitdauer für die Aktivierung des Zustands <code>Safestate</code> bei<br>Kommunikationsausfall (0 = keine Timeout-/Safe-State-<br>Funktion, ganzzahlige Vielfache von 1s, mindestens 5s)</p> |
| Input Const | `tTimeUpdateSetp`    | `TIME`             | TIME#0ms   | <p>Updateintervall für die Vorgänge, die durch den Eingang<br><code>xUpdateSetp</code> beeinflusst werden</p>                                                                                   |
| Input Const | `tTimeUpdateActual`  | `TIME`             | TIME#3s0ms | <p>Updateintervall für die Vorgänge, die durch den Eingang<br><code>xUpdateActual</code> beeinflusst werden</p>                                                                                 |


---

# Agent Instructions
This documentation is published with GitBook. GitBook is the documentation platform designed so that both humans and AI agents can read, navigate, and reason over technical content effectively. Learn more at gitbook.com.

## Querying This Documentation
If you need additional information that is not directly available in this page, you can query the documentation dynamically by asking a question.

Perform an HTTP GET request on the current page URL with the `ask` query parameter, and the optional `goal` query parameter:

```
GET https://support.powerio.com/hub/codesys-hvac/hvac-modbus-library/functionblocks/powerio/powerio_t1_bsk1_xxx_eco_easy.md?ask=<question>&goal=<endgoal>
```

`ask` is the immediate question: it should be specific, self-contained, and written in natural language.
`goal` is optional and describes the broader end goal you are ultimately trying to accomplish on behalf of the user. GitBook uses it to tailor the answer towards what is most useful for that goal.

The response will contain a direct answer to the question and relevant excerpts and sources from the documentation.

Use this mechanism when the answer is not explicitly present in the current page, you need clarification or additional context, or you want to retrieve related documentation sections.