# POWERIO\_T1\_BSK1\_XXX\_EASY

## `POWERIO_T1_BSK1_XXX_EASY` (FB)

`FUNCTION_BLOCK` POWERIO\_T1\_BSK1\_XXX\_EASY

### Darstellung

<figure><img src="https://879424349-files.gitbook.io/~/files/v0/b/gitbook-x-prod.appspot.com/o/spaces%2FQR4vCFzt6ixgsqlR3pdR%2Fuploads%2FXPy6VqYEY4Y7FA9yyRtI%2FHVACModbus.POWERIO_T1_BSK1_XXX_EASY.png?alt=media&#x26;token=2625e7ba-ff3a-4296-ad5e-b68e5bf2f631" alt=""><figcaption></figcaption></figure>

InOut:

| Scope       | Name                 | Type               | Initial    | Comment                                                                                                                                                                                         |
| ----------- | -------------------- | ------------------ | ---------- | ----------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------- |
| Input       | `xEn`                | `BOOL`             | TRUE       | Freigabe / Sperrung der Kommunikation (TRUE = Freigabe)                                                                                                                                         |
| Input       | `byUnitId`           | `BYTE`             | 0          | Adresse des Geräts                                                                                                                                                                              |
| Input       | `xUpdateActual`      | `BOOL`             | FALSE      | <p>Aktualisierung der Istwerte (bei jeder ansteigenden Flanke<br>)</p>                                                                                                                          |
| Input       | `xUpdateSetp`        | `BOOL`             | FALSE      | <p>Aktualisierung der Sollwerte (bei jeder ansteigenden Flanke<br>)</p>                                                                                                                         |
| Input       | `xResError`          | `BOOL`             | FALSE      | <p>Reinitialisierung des Ausgangs <code>eErrorCodeCom</code> in den<br>fehlerfreien Zustand / Rücksetzung des Fehlerstatuses der<br>Brandschutzklappen (bei jeder ansteigenden Flanke)</p>      |
| Input       | `xFD1`               | `BOOL`             | FALSE      | <p>Festlegung des Zustands des Ausgangs der Brandschutzklappe 1<br>(FALSE = Geschlossen)</p>                                                                                                    |
| Input       | `xResAutoFDx`        | `BOOL`             | FALSE      | <p>Umschaltung der Handübersteuerung der Ausgänge für die<br>Brandschutzklappen in den Automatikbetrieb (bei jeder<br>ansteigenden Flanke)</p>                                                  |
| Input       | `xSendSysCommand`    | `BOOL`             | FALSE      | <p>Aktivierung der Übertragung des Systembefehls (Register 6)<br>(bei jeder ansteigenden Flanke UND wSysCommand > 0)</p>                                                                        |
| Inout       | `ModbusClient`       | `ModbusClientBase` |            | Client des Geräts                                                                                                                                                                               |
| Output      | `xFD1_Open`          | `BOOL`             |            | Rückmeldung - Brandschutzklappe 1 geöffnet (TRUE = Offen)                                                                                                                                       |
| Output      | `xFD1_Closed`        | `BOOL`             |            | <p>Rückmeldung - Brandschutzklappe 1 geschlossen (TRUE =<br>Geschlossen)</p>                                                                                                                    |
| Output      | `xFD1_Fb`            | `BOOL`             |            | <p>Rückmeldung - Zustand des Ausgangs der Brandschutzklappe 1 (<br>FALSE = Geschlossen)</p>                                                                                                     |
| Output      | `eAOO_FD1`           | eManBin            |            | <p>Zustand der Handübersteuerung am Ausgang der<br>Brandschutzklappe 1</p>                                                                                                                      |
| Output      | `xAlarm`             | `BOOL`             | FALSE      | Sammelstörung (TRUE = Störung)                                                                                                                                                                  |
| Output      | `xAlarmCom`          | `BOOL`             | FALSE      | Sammelstörung - Kommunikation (TRUE = Störung)                                                                                                                                                  |
| Output      | `eErrorCodeCom`      | ModbusErrorCode    |            | Fehlercode - Kommunikation (0 = kein Fehler)                                                                                                                                                    |
| Output      | `stErrorCodeFD1`     | `STRING`           |            | <p>String mit den Bit-Nummern der aktiven Fehler der<br>Brandschutzklappe 1 (‘’ = kein Fehler)</p>                                                                                              |
| Output      | `xBusy`              | `BOOL`             |            | Kommunikationsanzeige (TRUE = Kommunikation)                                                                                                                                                    |
| Input Const | `xDIxInversion`      | `BOOL`             | FALSE      | <p>Festlegung der Invertierung der Digitaleingänge DIx (FALSE:<br>keine Invertierung // TRUE = Invertierung)</p>                                                                                |
| Input Const | `wSysCommand`        | `WORD`             | 0          | <p>Wert des zu übertragenden System-Befehls (FC06 - Register 6<br>) (0 = keine Funktion, Werte > 0 siehe Dokumentation<br>T1\_BSK1\_XXX)</p>                                                    |
| Input Const | `xFD1_SafeState_Sta` | `BOOL`             | TRUE       | <p>Zustand des Digitalausgang für die Brandschutzklappe 1 im<br>Safestate-Betrieb (TRUE = Geöffnet)</p>                                                                                         |
| Input Const | `xFD1_SafeState_En`  | `BOOL`             | FALSE      | <p>Freigabe / Sperrung des Digitalausgangs für die<br>Brandschutzklappe 1 für den Safestate-Betrieb (TRUE =<br>Freigabe)</p>                                                                    |
| Input Const | `tTimeSafeState`     | `TIME`             | TIME#0ms   | <p>Zeitdauer für die Aktivierung des Zustands <code>Safestate</code> bei<br>Kommunikationsausfall (0 = keine Timeout-/Safe-State-<br>Funktion, ganzzahlige Vielfache von 1s, mindestens 5s)</p> |
| Input Const | `tTimeUpdateSetp`    | `TIME`             | TIME#0ms   | <p>Updateintervall für die Vorgänge, die durch den Eingang<br><code>xUpdateSetp</code> beeinflusst werden</p>                                                                                   |
| Input Const | `tTimeUpdateActual`  | `TIME`             | TIME#3s0ms | <p>Updateintervall für die Vorgänge, die durch den Eingang<br><code>xUpdateActual</code> beeinflusst werden</p>                                                                                 |