WILO_BUS_COMMAND_CODE_SET

WILO_BUS_COMMAND_CODE_SET (ENUM)

TYPE WILO_BUS_COMMAND_CODE_SET : OFF

Attributes: qualified_only\

InOut:

Name
Initial
Comment

OFF

16#1

Local control locked

SET

16#2

Start of the lock period for local control

MANUAL

16#5

Local and communicative control possible simultaneously

SET_PRESET

16#6

Start of the lock period for local control, transfer of the parameter set ‘Preset’ after the lock period expires