EKMBDXB7V1_CURRENT_VALUES_1
EKMBDXB7V1_CURRENT_VALUES_1 (STRUCT)
TYPE EKMBDXB7V1_CURRENT_VALUES_1: STRUCT
InOut:
wFanSpeed
WORD
Fan speed (0 - 7)
wAirflowDirection
WORD
Airflow direction (0 - 7)
xThermoState
BOOL
Thermostat status (FALSE = Off, TRUE = On)
xHeatingState
BOOL
Status - Heating (FALSE = Off, TRUE = On)
xFanState
BOOL
Status - Fan (FALSE = Off, TRUE = On)
xNormalMode
BOOL
Normal operation (FALSE = Off or On with fault, TRUE = On - Normal)
xForcedShutdown
BOOL
Status - Forced Off (FALSE = none, TRUE = Forced Off)
xOperationState
BOOL
Status - On / Off (FALSE = Off, TRUE = On)
wMasterHeatCool
WORD
Master Heating / Cooling (0 = undefined, 1 = Slave, 2 = Master)
xDeIcingState
BOOL
Status - Defrosting / Warm start (FALSE = Off, TRUE = On)
wOperationMode
WORD
Current operating status (0 = Fan, 1 = Heating, 2 = Cooling)
wFilterSignState
WORD
Status - Filter sign (0 = Off, 1 - 15 = On)
wOperationModeSetting
WORD
Operating status setting (0 = Fan, 1 = Heating, 2 = Cooling, 3 = Auto, 4 = Ventilation, 7 = Dehumidifying)
rSetpTemp
REAL
Current setpoint temperature (-1279 … +1279) (/10 in degrees Celsius)
rRoomTemp
REAL
Current room temperature (-5119 … +5119) (/10 in degrees Celsius) (suction temperature)
Last updated