EKMBDXB7V1_CURRENT_VALUES_1

EKMBDXB7V1_CURRENT_VALUES_1 (STRUCT)

TYPE EKMBDXB7V1_CURRENT_VALUES_1 : STRUCT

InOut:

Name
Type
Comment

wFanSpeed

WORD

Fan speed ( 0 - 7 )

wAirflowDirection

WORD

Airflow direction ( 0 - 7 )

xThermoState

BOOL

Thermostat status ( FALSE = Off, TRUE = On )

xHeatingState

BOOL

Status - Heating ( FALSE = Off, TRUE = On )

xFanState

BOOL

Status - Fan ( FALSE = Off, TRUE = On )

xNormalMode

BOOL

Normal operation ( FALSE = Off or On with error, TRUE = On - Normal )

xForcedShutdown

BOOL

Status - Forced shutdown ( FALSE = none, TRUE = Forced shutdown )

xOperationState

BOOL

Status - On / Off ( FALSE = Off, TRUE = On )

wMasterHeatCool

WORD

Master Heat / Cool ( 0 = undefined, 1 = Slave, 2 = Master )

xDeIcingState

BOOL

Status - De-icing / Warm start ( FALSE = Off, TRUE = On )

wOperationMode

WORD

Current operating status ( 0 = Fan, 1 = Heating, 2 = Cooling )

wFilterSignState

WORD

Status - Filter indicator ( 0 = Off, 1 - 15 = On )

wOperationModeSetting

WORD

Operation mode setting ( 0 = Fan, 1 = Heating, 2 = Cooling, 3 = Automatic, 4 = Ventilation, 7 = Dehumidify )

rSetpTemp

REAL

Current target temperature ( -1279 … +1279 ) ( /10 in degrees Celsius )

rRoomTemp

REAL

Current room temperature ( -5119 … +5119 ) ( /10 in degrees Celsius ) ( Intake temperature )